Number
Program name
12
'SIREN'
13
'Fire output'
'Output FAULT'
14
'Fire LAMP'
15
'Alarm output 2'
16
'Turn on for a given time
17
before arming'
'Turn off for a given
18
time before arming'
'Turn on for a given time
19
when arming'
'Turn off for a given
20
time when arming'
'Turn on for a given time
21
when disarming'
'Turn off for a given
22
time when disarming'
'Turn on for a given time
23
if arming has failed'
'Turn off for a given
24
time if arming has
failed'
'Turn on for a given time
25
when auxiliary alarm'
10
Program description
If 'Fire alarm' then blink given time (1,5 s ON, 0,5 s OFF);
if 'Attention', then blink given time (0,5 s ON, 1,5 s OFF);
if 'Intrusion alarm', then ON for a given time;
else OFF output.
If 'Fire alarm' or 'Fire prealarm', then ON (close) outputs;
else OFF (open) output.
If there are zones in the states
'Disconnected alarm loop', "Relay disconnected", "Fire
trouble", "Loop open circuit", "Configuration error",
"Open relay output ", "Relay output short circuit", "Battery
failed", "AC power failed", "Power failed", "2-wire line
short circuit" or "2-wire line trouble"
or "Disarmed", "Disarmed and ready" "Disarmed and not
ready",
or "Arming has failed", then OFF (open) output.;
else ON (close) output.
If 'Fire alarm', 'Fire prealarm', 'Intrusion alarm', 'Entry
alarm' or "Arming has failed", then blink (0,5 s ON, 0,5 s
OFF);
if 'Disconnected alarm loop' or 'Fire alarm', then blink
(0,25 s ON, 1,75 s OFF);
if state of all relay associated zones is 'Zone armed', then
ON;
else OFF output.
If all zones are armed or disarmed, then ON;
else OFF output.
If at least one zone is in "Arming delay" state, then ON for
a given time;
else OFF output.
If at least one zone is in "Arming delay" state, then OFF
for a given time;
else ON output.
If at least one zone is armed, then ON for a given time;
else OFF output.
If at least one zone is armed, then OFF for a given time;
else ON output.
If at least one zone is disarmed, then ON for a given time;
else OFF output.
If at least one zone is disarmed, then OFF for a given time;
else ON output.
If at least one zone is in the state 'Arm has failed', then ON
for a given time;
else OFF output.
If at least one zone is in the state 'Arm has failed', then
OFF for a given time;
else ON output.
If at least one zone is in the state 'Auxiliary alarm', then
ON for a given time;
else OFF output.