These venting systems, in combination with the GF900 Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock
Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination
Locations" section.
Regency
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the GF900 using a flexible vent.
®
FPI Kit #
Length
Contains:
#946-515
1.2 m
1)
2)
3)
4)
5)
#946-516
3 m
6)
7)
8)
9)
Notes:
1) Liner sections should be continuous without any
joints or seams.
2) Only Flex pipe purchased from Regency
used for Flex installations
3) Horizontal vent must be supported every 0.9m.
4) Regency
®
Direct Vent System (Flex) is only approved
for horizontal terminations.
5) Flex system can only be used up to a maximum
continuous vent length of up to 3m. If longer runs