4.5.2 HE-45 Mounting Bolt Installation
The HE-45 uses 1/2-13 x 8"' bolts. Embed the bolts in 3500 psi reinforced concrete with a minimum
of 6"' thickness. The threaded end of the bolt should extend 2 inches from the surface of the
floor. Use the outboard bolt holes for standard installation, the inboard bolt holes for side by side
installations, or installations near a wall or other object that would prevent access to the outboard
holes. Refer to figure 4.7 on page 21.
Figure 4.7: HE-45 Mounting Detail
21