Models whose part number ends with a "240X" are fitted with a single-phase
isolating output transformer and are separately derived sources. The output
neutral is already bonded to ground on the output terminals with a Bonding
Jumper (see NEC 250-5d, 250-26, 250.91, 250.92). The output L1 and L2
terminals are not connected to the input L1 and L2.
CONNECTION
INPUT
OUTPUT @ 230V
OUTPUT @ 120V
BATTERY
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
CONNECTION
INPUT
OUTPUT @ 230V
OUTPUT @ 120V
BATTERY
SIZE GROUNDING (PROTECTIVE EARTH) CONDUCTORS EQUAL TO CIRCUIT CONDUCTORS
INPUT
UTILITY
L
1
INPUT TO UPS
NOTE 1
Grounding Electrode System
or Protective Earth System
GXT6000T / 10000T - 240X ONLY
GXT6000T-240X CONNECTIONS
CURRENT
RATING
27 AMPS
25 AMPS
50 AMPS
27 AMPS
GXT10000T-240X CONNECTIONS
CURRENT
RATING
44 AMPS
42 AMPS
83 AMPS
44 AMPS
NOTE 4
L
2
OUTPUT TO LOAD
Recommended
Wire Size
8 AWG (10 mm²)
8 AWG (10 mm²)
8 AWG (10 mm²)
8 AWG (10 mm²)
Recommended
Wire Size
6AWG (16 mm²)
6AWG (16 mm²)
6AWG (16 mm²)
6AWG (16 mm²)
OUTPUT
N
L
1
NOTE 2
14
Recommended External
Overcurrent Protection
40 AMPS
Recommended External
Overcurrent Protection
60 AMPS
OPTIONAL
BATTERY
L
2
OPTIONAL
BATTERIES
NOTE 3
+
-