Ensure safe operation
Gasoline is extremely flammable and explosive under
WARNING
certain conditions. Refuel in a well ventilated area with
the engine stopped.
Keep away from cigarette, smoke and sparks when
refueling the generator, Always refuel in a well-ventilated
location.
Wipe up spilled gasoline at once.
Connections for standby power to a building's
WARNING
electrical system must be made by a qualified electrician
and must comply with all applicable laws and electrical
codes. Improper connections can allow electrical current
from the generator to back feed into the utility lines. Such
back feed may electrocute utility company workers or
others who contact the lines during a power outage, and
when utility power is restored, the generator may
explode, burn, or cause fires in the building's electrical
system.
Always make a pre-operation inspection before you
WARNING
start the engine to prevent an accident or equipment
damage.
Place the generator at least 1m away from buildings
or other equipment during operation.
Operate the generator on a level surface. if the
generator is tiled, fuel spillage may result.
Know how to stop the generator quickly and
understand operation of all the controls. Never permit
anyone to operate the generator without proper
instructions.
Keep children and pets away from the generator
when it is in operation.
The generator is a potential source of electrical
shocks when misused; do not operate with wet hands.
Do not operate the generator in rain or snow and do
not let it get wet to avoid electric shock.
- -
13. APPENDIX
1. Modified coefficient table of ambient condition power
The conditions of generator rated output:
Altitude: 0 m
Ambient temperature: 25
Ambient modified coefficient: C (Relative humidity 30%)
Ambient temperature ( )
Altitude
(m)
25
30
0
1
0.98
500
0.93
0.91
1000
0.87
0.85
2000
0.75
0.73
3000
0.64
0.62
4000
0.54
0.52
Note: When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P =5KW, altitude is 1000m, ambient
temperature is 35
, relative humidity is 80%, the rated power of generator is:
P=P
(C-0.02) = 5
(0.82-0.02) = 4KW
N
Relative humidity: 30%
35
40
45
0.96
0.93
0.90
0.89
0.87
0.84
0.82
0.80
0.78
0.71
0.69
0.66
0.6
0.58
0.56
0.5
0.48
0.46
N
-
-

Hide quick links: