Baxi Platinum Combi 24 HE Installation & Servicing Instructions Manual page 20

Gas fired wall mounted condensing combination boiler
Table of Contents

Advertisement

20
Fig. 13
Fig. 14
7.0 Site Requirements
7.8
Flue Dimensions
The standard horizontal flue kit allows for flue lengths between
100mm and 685mm from elbow to terminal (Fig. 13).
The maximum permissible equivalent flue length is:
10 metres
7.9
Flue Trim
1. The rubber flue trim supplied may be fitted to either the
outside wall or on the inner wall of installation.
7.10
Terminal Guard (Fig. 14)
1. When codes of practice dictate the use of terminal guards,
they can be obtained from most Plumbers' and Builders'
Merchants.
2. There must be a clearance of at least 50mm between any
part of the terminal and the guard.
3. When ordering a terminal guard, quote the appliance name
and model number.
4. The flue terminal guard should be positioned centrally over
the terminal and fixed as illustrated.