Cooling
Temperature Condition (
O
F)
Indoor
Outdoor
80.6/66.6
95/75.2
Heating
O
Temperature Condition (
F)
Indoor
Outdoor
70/60
47/43
68/59
44.6/42.8
Notes:
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U-Bend.
(2) Length of connecting tubing = 24.6 .
(3) P = Pressure PSI
T1 = Inlet and Outlet Temperature for Evaporator
T2 = Inlet and Outlet Temperature for Condenser
Product Introduction
Operation Data
Pressure
Model
(
PSI)
9K
135
12K
152
18/24K
131-160
Pressure
Model
(
PSI)
9K
401
12K
308
18/24K
319-348
Heat Exchanger
Pipe Temperature
T1 (
O
F)
T2 (
O
F)
57.2
98.6
59
98.6
167-181.4 to
46.4-51.8 to
98.6-118.4
51.6-57.2
Heat Exchanger
Pipe Temperature
O
O
T1 (
F)
T2 (
F)
113
41
107.6
41
167-181.4
33.8-37.4 to
98.6-113
35.6-42.8
Indoor Fan
Outdoor Fan
Mode
Mode
Turbo
High
Turbo
High
Turbo
High
Indoor Fan
Outdoor Fan
Mode
Mode
Turbo
High
Turbo
High
Turbo
High
Compressor
Speed
(rps)
46
70
75
Compressor
Speed
(rps)
56
73
75
15