Wiring Example; Installation Of The Decoration Panel; Field Setting - Daikin FXFQ20AVEB Installation And Operation Manual

Vrv system air conditioners
Hide thumbs Also See for FXFQ20AVEB:
Table of Contents

Advertisement

W
IRING EXAMPLE
Fit the power supply wiring of each unit with a switch and fuse as
shown in
figure
17.
1
Power supply
2
Main switch
3
Power supply wiring
4
Unit transmission wiring
5
Switch
6
Fuse
7
BS unit (REYQ only)
8
Indoor unit
9
Remote controller
Complete system example (3 systems)
See figures 13,
14
and 15.
1
Outdoor unit
2
Indoor unit
3
Remote controller (Optional accessories)
4
Most downstream indoor unit
5
For use with 2 remote controllers
6
BS unit
When using 1 remote controller for 1 indoor unit. (Normal
operation)
(See figure
13).
For group control or use with 2 remote controllers
When including BS unit
(See figure
NOTE
It is not necessary to designate indoor unit address
when using group control. The address is automatically
set when the power is activated.
Precautions
1.
A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
2.
For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.
3.
Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.
I
NSTALLATION OF THE DECORATION PANEL
Refer to the installation manual delivered with the decoration panel.
After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop.
F
IELD SETTING
Field setting must be made from the remote controller in accordance
with the installation condition.
Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".
For setting and operation, refer to the "Field setting" in the
installation manual of the remote controller.
FXFQ20~125AVEB
VRV System air conditioners
3P320142-1A – 2012.10
(See figure
14).
15).
Summary of field settings
Mode
First
No.
code
(Note 1)
No. Description of setting
Filter contamination
- Heavy/Light
= Setting to define
time between 2 filter
cleaning display
indications. (When
Long-life
0
contamination is
filter
high, setting can be
changed to half the
time inbetween 2
filter cleaning
display indications.)
2
Thermostat sensor selection
10
(20)
Setting for display of time
3
between 2 filter cleaning display
indications
Information to I-manager,
5
I-touch controller
Thermostat sensor in group
6
control
Output signal X1-X2 of the
0
optional KRP1B PCB kit
ON/OFF input from outside
(T1/T2 input) = Setting when
1
forced ON/OFF is to be
operated from outside.
Thermostat differential
12
2
changeover = Setting when
(22)
remote sensor is used.
Fan setting during thermostat
3
OFF at heating operation
Differential automatic
4
changeover
5
Auto-restart after power failure Disabled
Setting for air outlet
other
velocity
models
0
This setting is to be
FXFQ125
changed in function
only
of ceiling height.
Selection for air flow direction
13
This setting is to be changed
1
(23)
when blocking pad optional kit
is used.
Airflow direction range setting
This setting is to be changed
4
when range of swing flap
movement needs to be
changed.
Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected,
indoor units can also be set individually.
Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01,
10-2-02 or 10-2-03 have priority.
Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have
priority.
Note 7 : More settings for Differential automatic change over temperatures are:
Second code No.
05
4°C
06
5°C
07
6°C
08
7°C
When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.
Second code No. (Note 2)
01
02
03
±2,500 hrs.
±1,250 hrs.
Use both the
unit sensor (or
Use unit sensor
remote sensor if
Use remote
only (or remote
installed) AND
controller
sensor if
the remote
sensor only.
installed).
controller
(See note 5+6)
(See note 5+6)
sensor.
(See note 5+6)
Display
Do not display
Only unit sensor
Sensor value as
value (or remote
set by 10-2-0X
sensor value if
or 10-6-0X.
installed).
Use both the
unit senor (or
Use unit sensor
remote sensor if
only (or remote
installed) AND
sensor if
the remote
installed).
controller
(See note 6)
sensor. (See
note 4+5+6)
Thermostat-on
+ compressor
Operation
run
ON/OFF
Forced OFF
operation
1°C
0.5°C
OFF
LL
Set speed
(See note 3)
0°C
1°C
2°C
Enabled
≤2.7 m
>2.7 ≤3.0 m
>3.0 ≤3.5 m
≤3.2 m
>3.2 ≤3.6 m
>3.6 ≤4.2 m
4-way flow
3-way flow
Upper
Medium
Lower
Installation and operation manual
04
Mal-
function
3°C
(See
note 7)
8