JOHNSON SYSTEMS JS-ICON 2410 User Manual page 22

Dimmer rack
Table of Contents

Advertisement

17. VOUT LIM
01<127.5
24<127.5
24>127.5
24>100.0
24<100.0
18. REGULATE
ENABLED
DISABLED
19. ANA MODE
A01<NORM
A04<NORM
A04<SHED
20. ANA PTCH
A01<C01
A04<C01
A04>C01
A04>C24
A04>C24 *
A04<C24 *
22
Set the maximum RMS output voltage for each dimmer.
Limiting the maximum RMS voltage can greatly improve lamp life.
Press EXECUTE to enter the menu.
Displays the dimmer (01) and its current maximum output voltage level (127.5).
Press MENU (
) to select the desired dimmer number from 01 to 24.
Press EXECUTE to toggle the pointer (< >) to select the output voltage level.
Press MENU (
) to adjust the output voltage level in 0.5 Volt increments.
Press EXECUTE to toggle the pointer (< >) to select another dimmer number.
Press ESCAPE to exit the menu and save the desired dimmer curves.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 2 minutes of inactivity and save.
Enable or disable the dimmer output voltage regulation.
With the on-board output voltage regulation feature enabled the maximum RMS
output is limited to 118 Volts. Voltage regulation automatically adjusts the internal
control level to compensate for any line voltage fluctuations.
Press EXECUTE to toggle regulation from ENABLED to DISABLED.
Press EXECUTE to toggle regulation from DISABLED to ENABLED.
Any change in the configuration is automatically saved.
Configure the analog inputs for normal or load shed mode.
Each of the four (4) analog inputs can be independently configured for normal
(NORM) or load shed (SHED) mode of operation.
Normal (NORM) mode sets the analog input for 0-10VDC operation. The analog
voltage level sensed sets the level for the selected dimmer outputs.
Load shed (SHED) mode is used as a power management interface to building
management systems (BMS). Contact closure devices such as a photocell or
maintained switch contact may be used to trigger the analog input. When a voltage
of 5.5VDC to 12VDC is sensed on the analog input the selected dimmer outputs are
disabled (set to zero output level). The selected dimmer outputs are enabled when
the voltage sensed on the analog input drops to below 4.5VDC.
Press EXECUTE to enter the menu and set the mode for each analog input.
Displays the active analog input (A01) and current mode setting (NORM).
Press MENU (
) to select the desired analog input to configure from 01 to 04.
Press EXECUTE to toggle from normal (NORM) to load shed (SHED) mode.
Press ESCAPE to exit the menu and save the desired analog input modes.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 2 minutes of inactivity and save.
Patch the analog inputs to any combination of control channels.
Press EXECUTE to enter the menu and activate analog patch mode.
Displays the active analog input (A01) and control channel (C01).
Press MENU (
) to select the desired analog input to patch.
Press EXECUTE to toggle the pointer (>) to select the control channel.
Press MENU (
) to select the desired control channel from 01 to 24.
Press EXECUTE to patch and flag (*) the control channel to the analog input.
Press ESCAPE to toggle the pointer (< >) to select another analog input.
Press ESCAPE to exit the menu and save the desired analog patches.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 2 minutes of inactivity and save.