Summary of Contents for JOHNSON SYSTEMS JS-ICON 2410
Page 1
User Manual JS-ICON Series ™ Dimmer Rack JS-ICON 2410 ™ JS-ICON 2413 ™ JS-ICON 1220 ™ JS-ICON 1210/620 ™ JOHNSON SYSTEMS INC. www.johnsonsystems.com...
Contents Warranty ......................2 For Technical Assistance .................2 Introduction ......................3 Characteristics ....................4 Installation .......................5 Power Supply Connection Details ..............6 Ground Connection Details ................8 Dimmer Output ....................9 Control Input/Output ..................10 MADD-24 (Multiple Application Dimmer Driver) ..........11 User Interface ....................12 System Status - LED Indicators..............13 System Status - LCD Display ................13 Quick Programming Reference to System Configuration Menu Items ..15 Detailed Programming of System Configuration Menu Items......16...
Introduction JS-ICON Series wall-mount dimmer racks represent the ultimate ™ value in hi-performance dimming! Next generation “system-on-a-chip” technology coupled with state-of-the-art inductor technology provides unsurpassed quality in professional grade SCR dimming. Advanced next generation hardware and software designs reduce stand-by power consumption to less than 1 Watt, allowing for compliance with the International Energy Agency’s “One Watt Initiative”...
Installation Mounting The JS-ICON Series dimmer racks can be mounted to any wall surface capable of supporting its weight of approximately 66 lbs (30 kg) for each rack. Four 1/4" (6mm) screws or bolts are required to fasten the rack safely to the wall (see the drawing below for mounting locations and dimensions).
Power Supply Connection Details The JS-ICON ™ Series dimmer racks are capable of various 120V power supply configurations. The contractor termination section is located on the left-hand side. Knockouts on the top and bottom of the chassis are provided for wire/conduit entry to the power terminals. The phase power terminals are mounted directly onto copper bussbars, used to distribute current to each dimmers circuit breaker.
Page 7
Power Supply Connection Details Power Supply Configurations - Single Phase: 120/240 VAC, 1Ø, 4-Wire up to 100 Amps per phase. Maximum 24.0kW total. Use wire size #14 to #1/0 AWG. Strip insulation length to 0.65" (16.5mm). Torque power terminals (A, B, C) to 45-50 IN-LBS (5.0-5.6 NM). ∅...
Load Circuit Neutral Power Supply Connection Details Output Terminals Neutral Power Distribution Block Neutral Input Terminal • Use wire size #14 to #1/0 AWG. Strip insulation length to 0.65" (16.5mm). • Torque neutral terminal(s) to 45-50 IN-LBS (5.0-5.6 NM). Capable of single or dual rated neutral termination. The neutral terminal may be mounted on the top or bottom of the distribution block to facilitate top or bottom wire entry.
Signal Distribution Board Control Input/Output DMX A I/O DMX B I/O JS-ICON ™ Series dimmer racks come with a variety of control input and output (I/O) capabilities. All I/O connections are terminated on the Signal Distribution Board, located on the right-hand side of the dimmer rack. BUMP REMOTE Breakaway type connectors are supplied for all I/O connections.
Over-Temperature Input (Normally Open) FIRE • Terminate (O/T) on J11 connector. SCTY • Disables all dimmer outputs when contact/switch is closed. MAINTAINED • Controlled via a maintained contact/switch to low-voltage common (COM). NORMALLY OPEN SWITCH CONTACT Fire Alarm Input (Normally Open) •...
User Interface LCD Display The user interface provides access to all programming and configuration settings. System status is easily visible on the LCD display and LED Infrared LED indicators. All JS-ICON Series dimmer racks are equipped with a user ™ Programming interface connected to the Signal Distribution Board via a 34-pin ribbon Switches...
System Status - LED Indicators RUN (Green) Illuminates when the power is on, and the microcontroller status is in normal run mode. The LED flashes once every 2 seconds when the system is in STANDBY mode. ØA, ØB and ØC (Green) Illuminates when the line voltage power is within the acceptable range of 100-130 VAC for each phase, and the zero-cross reference circuitry is functioning properly.
Page 14
INF HOLD Displayed when DMX is disconnected, and the systems predetermined DMX status hold (SH) time is set for infinite (INF) hold. Refer to menu item “SH TIME” on page 21 for further details. SCENE:XX Displays the scene (1 to 24) that is currently activated. Refer to menu item “L-BUTTON” on page 24 for further details.
Quick Programming Reference to System Configuration Menu Items 1. SCENESET Enable and setup 24 different backup scenes. 2. FADETIME Set the fade time for each of the 24 scenes from 0 to 99 seconds. 3. SNAPSHOT Record DMX levels into the backup scenes. 4.
Detailed Programming of System Configuration Menu Items The programming switches can be locked out to prevent inadvertent configuration NOTE: changes. To toggle between “LOCKED!!” and “UNLOCKED” press and hold down the EXECUTE and then ESCAPE switches at the same time for 4-5 seconds. The sequence of the following system configuration menu items appear as the MENU DOWN ( ) switch is pressed.
Page 17
SNAPSHOT Record DMX levels into the backup scenes. Provides a quick and easy way to save control channel levels into each of the 01 to 24 backup scenes using a DMX source. Press EXECUTE to enter the menu and activate snapshot mode. SAVE >01 Press MENU ( ) to select a different scene from 01 to 24.
Page 18
DMX MODE Configure the mode of the on-board DMX protocol manager. There are five different mode settings for the DMX protocol manager. Priority A (PTY A) and Priority B (PTY B) modes are intended for the implementation of a backup DMX source. Priority A (PTY A) sets the DMX A input as the priority, and ignores the DMX B input when the DMX A input is active.
Page 19
10. DMXB TRM Enable or disable termination on the DMX B input. Activates and deactivates a 120Ω termination resistor. DMX termination is indicated on the LCD display when DMX is being received. When the DMX B input is not terminated (DISABLED) the LCD display will read AXXXBXXX. When the DMX B input is teminated (ENABLED) the LCD display will read AXXX XXX.
Page 20
If a dimmer is patched to both DMX A and DMX B input channels, the DMX levels are merged and highest-takes-precedence (HTP). Press EXECUTE to enter the menu and configure the DMX A patch. Press MENU ( ) to scroll through and select the patching method. MANUAL? Press EXECUTE to patch each of the dimmers manually (MANUAL).
Page 21
14. SH TIME Set the DMX status hold time from 0 to 99 minutes or infinite. When DMX is disconnected the system will hold the status of the last received DMX levels for the selected amount of time. When activated, the LCD display shows a countdown of the status hold time or infinite hold.
Page 22
17. VOUT LIM Set the maximum RMS output voltage for each dimmer. Limiting the maximum RMS voltage can greatly improve lamp life. Press EXECUTE to enter the menu. 01<127.5 Displays the dimmer (01) and its current maximum output voltage level (127.5). 24<127.5 Press MENU ( ) to select the desired dimmer number from 01 to 24.
Page 23
21. ANA TEST View the control level for each of the analog inputs. The analog voltage level for the 4 analog inputs can be tested and viewed as a percentage or hexadecimal value. The level displayed is proportional to the 0-10VDC analog input where 5VDC is 50%.
Page 24
A+D< 001 Displays the active trigger mode as analog and DMX (A+D<) channel 001. A+D> 001 Press EXECUTE to toggle the pointer (>) and select the DMX channel. A+D> 512 Press MENU ( ) to change and select the DMX channel from 001 to 512. A+D<...
Page 25
30. F-ALARM Select the level and control channels triggered by the fire alarm input. When a contact is sensed on the fire alarm input, the selected control channels are triggered on to the selected output level from 0% to 100%. The fire alarm input is merged with the DMX and analog inputs with highest takes precedence (HTP).
Page 26
33. POLARITY Set the PWM output control polarity. Locked for factory use only! This menu is only used when swapping the MADD-24 controller between different models of JS-ICON Series dimmer racks. ™ Press EXECUTE to enter the menu and configure the polarity mode. DISABLED This menu is for factory use, and is disabled for the end user.
Page 27
39. HARD-KEY View the microcontroller’s unique six-character hard-key code. JS-ICON Series dimmer racks may be shipped with an invalid hard-key code of ™ 000000. A valid hard-key must be entered before the run time (RTIME) counter reaches 2160 hours / 90 days. If the run time expires without a valid hard-key the LCD display will show a runtime counter error (RTC ERR!) and all dimmer control outputs will be disabled.
Page 28
43. FW-LOAD Load new firmware into the MADD-24 via the EEPROM memory module. If a firmware update is required, Johnson Systems Inc. may supply an EEPROM memory module with the latest firmware version. The firmware EEPROM memory module can be inserted into PORT1 on the MADD-24 board and the firmware can be loaded into the microcontroller.
Page 29
RESTART When parameter restore is complete, the system restarts. SERIAL # Displayed when the silicone serial number on the EEPROM memory module is a mismatch with the silicone serial number on the MADD-24 microcontroller. PROCEED? Press EXECUTE to proceed. NO MEM! Displayed if an EEPROM memory module is not detected.
Page 30
SCENE>FL Press MENU ( ) to select the desired scene (01 to 24) or all scenes (FL). V-LIMIT? Prints the output voltage limit settings for each of the 24 dimmer outputs. DCPATCH? Prints the configuration settings for the dimmer to channel patch. FD-TIME? Prints the fade time settings for each of the 24 scenes.
Important Hard-key Information Series dimmer racks may be shipped with an invalid hard-key code of 000000. A valid hard-key must be ICON ™ entered before the run time (RTIME) counter reaches 2160 hours / 90 days. If the run time expires without a valid hard-key, the LCD display will show a runtime counter error (RTC ERR!) and all dimmer control outputs will be disabled.
Troubleshooting Reference This manual is accurate at time of printing and subject to revisions and technical updates as required without prior notice. Please visit www.johnsonsystems.com for applicable updates. www.johnsonsystems.com...
Page 33
Troubleshooting Reference This manual is accurate at time of printing and subject to revisions and technical updates as required without prior notice. Please visit www.johnsonsystems.com for applicable updates. www.johnsonsystems.com...
Page 34
JSI-ICON Series Dimmer/Relay Racks ™ JS-ICON 2410 JS-ICON 2413 ™ ™ 24 x 10 Amp (1200 Watt) dimmers 24 x 13 Amp (1560 Watt) dimmers JS-ICON 1220 JS-ICON 1210/620 ™ ™ 12 x 20 Amp (2400 Watt) dimmers 12 x 10 Amp (1200 Watt) + 6 x 20 Amp (2400 Watt) dimmers User Manual JS-ICON...