Mitsubishi Electric City Multi PCFY-P15NGMU-E Technical & Service Manual page 32

Split-type, heat pump air conditioners
Hide thumbs Also See for City Multi PCFY-P15NGMU-E:
Table of Contents

Advertisement

OPERATING PROCEDURE
9. Removing the drain pan
(1) Remove the air intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel. Remove the screws of the right
and left side drain pan.
(5) Remove the insulation in centre of the drain pan, and
after removing the screw, remove the drain pan.
(Note)
Please note that there might be drain left in the drain pan
when you remove the drain pan.
10. Removing the guide vane
(1) Remove the intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel.
(5) Remove the drain pan.
(6) Remove the screw from the guide vane, then remove the
guide vane.
11. Removing the Auto vane
(1) Remove the intake grille.
(2) Remove the left side panel.
(3) Remove the left side box.
(4) Remove the under panel.
(5) Remove the screw from the auto vane.
(6) Slide the auto vane to the right side and pull the auto
vane out.
PHOTOS & ILLUSTRATIONS
Photo 8
Screw
Drain pan
Photo 9
Drain pan
Guide vane
Photo 10
Auto vane
32
Screws
(Insulation)
Screw
Screw
Screw