7-2. DRY OPERATION

TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
˚F˚C
˚F˚C
ONLY1Hr.
TEMP.
MENU
ON/OFF
BACK
MONITOR/SET
DAY
PAR-21MAA
CLOCK
OPERATION
Control modes
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
1. Thermoregulating
function
1-2. Frozen prevention control
2. Fan
Indoor fan speed depends on the compressor conditions.
Note: Remote controller setting is not acceptable.
3. Drain pump
Same control as COOL operation
4. Vane
Same control as COOL operation
(up/ down vane change)
<How to operate>
1 Press POWER ON/OFF button.
Hr
ON
2 Press the operation MODE button to display DRY.
AFTER
OFF
FUNCTION
FILTER
3 Press the TEMP. button to set the desired temperature.
WEEKLY
SIMPLE
AUTO OFF
NOTE: The set temperature changes 2°F when the
ON/OFF
FILTER
CHECK
TEST
CLEAR
Setting the Dry thermo by the thermoregulating signal and the
room temperature (TH1).
Dry thermo ON Room temperature ] desired temperature + 2°F
Dry thermo OFF Room temperature [ desired temperature
3 min. passed since starting operation
Room
temperature
Thermoregulating signal Room temperature (T1)
ON
Over 64°F
OFF
Less than 64°F
No control function
Dry thermo
Fan speed notch
[Low]
ON
Stop
OFF
pressed one time. Dry 67 to 87°F.
Control details
T1 ] 83°F
83°F > T1 ] 79°F
79°F > T1 ] 75°F
75°F > T1
Unconditional
Dry thermo OFF
17
or
Dry thermo
Dry thermo
ON
OFF
time (min)
time (min)
9
3
3
7
5
3
3
3
3
10
button is
Remarks