Fujitsu AB*14LBAJ Service Instruction page 90

Split type room air conditioner universal floor / ceiling / duct / cassette wall mounted / floor type inverter multi
Hide thumbs Also See for AB*14LBAJ:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 4
Outdoor unit Electronic Expansion Valve
( EEV )
Check Point 1 : Check Connections
Check connection of connector
( Loose connector or open cable )
For AO*18LMAK2 / AO*24LMAM2
EXPANSION
RED
1
VALVE COIL A
BROWN
2
BLUE
3
CN27
E V
ORANGE
4
YELLOW
5
WHITE
6
EXPANSION
RED
1
VALVE COIL B
BROWN
2
BLUE
3
CN27
E V
ORANGE
4
YELLOW
5
WHITE
6
Check Point 2 : Check Coil of EEV
Remove connector, check each winding
resistance of Coil.
Read wire
White - Red
Yellow - Brown
46
Orange - Red
Blue - Brown
If Resistance value is abnormal, replace EEV.
For AO*30LMAW4
CN27
CN50
CN51
CN52
Resistance value
4
at 20°C
EXPANSION
RED
1
VALVE COIL A
BROWN
2
BLUE
3
E V
ORANGE
4
YELLOW
5
WHITE
6
EXPANSION
BLACK
RED
1
1
1
VALVE COIL B
WHITE
BROWN
2
2
2
WHITE
BLUE
3
4
3
E V
WHITE
ORANGE
5
4
4
WHITE
YELLOW
6
5
5
WHITE
WHITE
6
6
7
WHITE
EXPANSION
BLACK
RED
1
1
1
VALVE COIL C
GREEN
BROWN
3
2
2
GREEN
BLUE
4
3
3
E V
GREEN
ORANGE
5
4
4
GREEN
YELLOW
6
5
5
GREEN
WHITE
6
6
7
GREEN
EXPANSION
BLACK
RED
1
1
1
VALVE COIL D
GREEN
BROWN
3
2
2
GREEN
BLUE
4
3
3
E V
GREEN
ORANGE
5
4
4
GREEN
YELLOW
6
5
5
GREEN
WHITE
6
6
7
GREEN
Check Point 3 : Check Voltage from Main PCB.
Remove Connector and check Voltage (DC12V)
If it does not appear, replace Main PCB.
Check Point 4 : Check Noise at start up
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.