Outdoor Fan Control - Fujitsu AB*14LBAJ Service Instruction

Split type room air conditioner universal floor / ceiling / duct / cassette wall mounted / floor type inverter multi
Hide thumbs Also See for AB*14LBAJ:
Table of Contents

Advertisement

4. OUTDOOR FAN CONTROL

1. Outdoor Fan Motor
Following table shows the fan speed of the outdoor unit.
( Table 3 : Fan speed of the outdoor unit )
AO*18LMAK2
AO*24LMAM2
AO*30LMAW4
For AO*18LMAK2/ 24LMAM2
*
When the outdoor heat exchanger tenperature is lower than 2°C,
the fan speed switches to 780rpm on heating mode.
For AO*30LMAW4
*
It runs at 500rpm for 20 seconds after starting up the outdoor fan.
When the outdoor heat exchanger tenperature is lower than 2°C,
the fan speed switches to 780rpm on heating mode.
Cooling
780/ 420 rpm
820/ 780/ 400/ 300/ 200 rpm
01-11
Heating
780/ 420 rpm
850/ 780/ 400/ 300/ 200 rpm