Fujitsu AB*14LBAJ Service Instruction page 68

Split type room air conditioner universal floor / ceiling / duct / cassette wall mounted / floor type inverter multi
Hide thumbs Also See for AB*14LBAJ:
Table of Contents

Advertisement

Trouble shooting 20
OUTDOOR UNIT Error Method:
Compressor Start-up error
(Permanent Stop)
Detective Actuators:
Outdoor Unit Main PCB Circuit
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure
Check Point 1 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
On start-up the compressor, when detected rotor position is out of phase
with actual rotor position more than 90 degrees,the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If
and
repeats 5 times, the compressor stops permanently.
02-30