1.3.2 Burners

The water heaters are suitable for oil-fired burners.
The water heaters have been examined and tested with
the following front-mounted burners from Riello:
The burners for the SOF 70 700 heaters must be fitted
HEATER
SOF 85 220
SOF 85 260
SOF 85 300
SOF 75 390
SOF 75 470
SOF 70 700
with a special fire tube in view of the higher
temperatures in the heater's combustion chamber. The
manufacturer has already fitted the special fire tube to a
burner supplied direct with the water heater. Otherwise
the special fire tube must be retrofitted. Please consult
your supplier on this matter.
The heaters are also suitable for front-mounted burners
from other manufacturers, provided that the following
conditions are met:
-
The front-mounted burners must be EC approved,
-
The flame length of the front-mounted burner must
be less than the diameter of the heater's combustion
chamber. This diameter is 510 mm for all heaters,
-
For the SOF 75 470 and SOF 70 700 a starting load
of 120 kW at maximum (according to EN 676) must
be set. Consult to this end the instruction manual of
the front-mounted burner used,
-
The air-proving switch must be set in such a way that
it cuts out before the CO contents of the flue gas
reaches a value of 2000 ppm.
-
The maximum burner pressure of the heater
amounts to 25 Pa across the entire range. The
selected burner must be able to supply at least this
pressure.
Before installing and commissioning the selected burner,
you must consult the front-mounted burner's instruction
manual.
8
OIL-FIRED BURNER
MODEL
RG 2
RG 2
RG 3
RG 3
RG 3
RG 4S
TYPE
377 T1
377 T1
393 T1
393 T1
393 T1
396 T1