Pulsar PG7500B Owner's Manual page 25

7500 watt generator pulsar pg7500b
Table of Contents

Advertisement

Installation (cont'd)
Supporting and Mounting
Mount the generator on a concrete slab capable of supporting the weight of the generator. The
slab must extend on all sides beyond the frame by at least one foot. Contact a cement contractor
for slab specifications if necessary. Attach the frame to the concrete slab using 3/8" diameter
expansion anchor bolts (not supplied).
Grounding
NOTE: IT IS RECOMMENDED THAT ONLY A TRAINED AND LICENSED
ELECTRICIAN PERFORM THIS PROCEDURE
Connect a #6 AWG grounding wire (not included) from the ground connector (8) on the generator
to a grounding rod (not included) that has been driven at least 24 inches deep into the earth. The
grounding rod must be an earth-driven copper or brass rod (electrode) which can adequately
ground the generator.
Owner's Manual
6
25

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PG7500B and is the answer not in the manual?

Table of Contents