Cleaning The Condensate Trap; Combustion Parameters - Potterton Sirius two WH Instruction Manual

90 & 110 kw
Table of Contents

Advertisement

7,5 ±1 for model WH 90
5,0 ±1 for model WH 110

18.3 CLEANING THE CONDENSATE TRAP

Unscrew the lower section of the water condense trap.
• Clean the bottom of the trap by flushing it out with water.
• Fill the lower section with water until about 10 mm below the upper
edge.
• Fasten the lower section onto the condense trap again.
Do not operate the boiler with empty condense trap to avoid risk
of poisoning through the gas combustions.

18.4 COMBUSTION PARAMETERS

To measure combustion efficiency and the emissions of the products of combustion, the boiler is
fitted with two dedicated test points. One connection point is connected to the flue gas discharge
circuit ( A), and allows monitoring of the quality of the combustion products and the combustion
efficiency. The other is connected to the combustion air intake circuit ( B), allowing checking of
any recycling of the combustion products in case of coaxial pipelines. The following parameters
can be measured at the connection point on the flue gas circuit:
• temperature of the combustion products;
• oxygen (
) or carbon dioxide (
• carbon monoxide (
) concentration.
The temperature of the combustion air must be measured on the test point located on the air intake flue (B) by inserting the me-
asurement sensor by about 90 mm (C).
To enable the " CHIMNEY SWEEP MODE" consult section 12.3.
CG_2190
) concentration;
19
IGNITION
ELECTRODE
FLAME DETECTION
PROBE
CONDENSATE DRAIN
(Uncrew to clean it)
BURNER
BURNER SURFACE
INSULATION
CR_0510
A
B
C
7108686.02 (1-11/12)