Special Functions; System Air Extraction Function; Commissioning Function; Chimney Sweep Mode - Potterton Sirius two WH Instruction Manual

90 & 110 kw
Table of Contents

Advertisement

11.2.8 AGU 2.550
Use the AGU 2.550 , already installed in the boiler, to send information from the boiler
as described below to a BMS panel.
ELECTRICAL CONNECTION
Power supply (230V 50Hz AC) connected to the boiler terminal
X1 (L-N)
X1 (QX21)
X1 (QX22-N)
X1 (QX23-N)
X2 (H2-M)

12. SPECIAL FUNCTIONS

12.1 SYSTEM AIR EXTRACTION FUNCTION

This function is used to facilitate the elimination of the air inside the heating circuit when the boiler is first installed or after mainte-
nance when the water is drained from the primary circuit and re-filled.
To enable the system air extraction function press buttons
together for 6 seconds. When the function is active, On appears on the display for a few seconds, followed by programme
row 312.
The electronic board will activate a pump on/off cycle lasting 10 minutes. The function will automatically stop at the end of the
cycle. To manually exit this function, press the above buttons together for 6 seconds once again.

12.2 COMMISSIONING FUNCTION

To commissioning the gas valve, proceed as follows:
• Press buttons
and
seconds followed by programme row "304" alternated with the % of boiler power.
• Press
to gradually adjust power (sensitivity 1%) 100% for high fire and 0% for low fire.
• To exit press both buttons together for at least 6 seconds, as described in point one.
Press
to display the instantaneous flow temperature for 15 seconds.

12.3 CHIMNEY SWEEP MODE

When this function is enabled, the boiler generates maximum heating power. To enable the function, proceed as follows:
• press
together for 6 seconds. The display shows "303" alternated with the power output of the boiler.
• Press
and
to adjust boiler power 1=minimum, 2=maximum DHW, 3=maximum heating.
• To exit press both buttons together for at least 6 seconds, as described in point one.

13. FAULTS THAT CANNOT BE RESET BY THE USER

In case of FAULTS that cannot be reset by pressing
RESET attempts by the user) RESET the board by pressing the black button ( R) located under
the rubber cap (symbol

14. PARAMETER SETTINGS

To programme the parameters of the boiler electronic board, proceed as follows:
• Press
together and hold them down for 6 seconds until programme row "P02" appe-
ars on the display alternated with the set value (°C);
• Press
and hold down for 6 seconds until "On" appears on the display. Release the but-
ton and "P01" appears on the display;
• Press
to scroll the list of parameters;
• Press
, the value of the selected parameter begins flashing, press
• Press
to confirm the value or press
Further information concerning the parameters listed in the following table are supplied together with the required acces-
sories.
7108686.02 (1-11/12)
block M1 (C+M)
Not used
Boiler OPERATION (light on = run)
Boiler ALARM (light on = lockout)
INPUT Electrical Signal 0÷10 V
together for at least 6 seconds. When the function is enabled, the displays shows "On" for a few
(such as E151 or exceeding 5 manual
) of the front control panel (figure to side).
to exit without saving.
230 V
(Boiler M1)
to change the value;
14
ALARM (LOCKOUT)
SIGNAL LAMP 230V
STATUS (RUN)
SIGNAL LAMP 230V
3
0÷10 V
Input Signal