Desa E18N Owner's Manual page 17

Unvented (vent-free)
Table of Contents

Advertisement

INSTALLATION
Continued
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 18).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas,
or using compressed air.
3. Check all joints from gas meter to equipment
shutoff valve for natural gas or propane/LP
supply to equipment shutoff valve for propane/
LP (see Figure 19). Apply noncorrosive leak
detection fluid to all joints. Bubbles forming
show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 18).
2. Open main gas valve located on or near gas
meter for natural gas or open propane/LP
supply tank valve.
3. Make sure control knob of heater is in the OFF
position.
4. Check all joints from equipment shutoff
valve to thermostat gas valve (Thermostat-
Controlled Models), to control valve (Manu-
ally-Controlled Models), or to gas control
(Remote-Ready Models) (see Figures 19 and
20). Apply noncorrosive leak detection fluid
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, page 19).
Check all other internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appli-
ance, page 20 for Thermostat-Controlled mod-
els, page 22 for Manually-Controlled Models,
or page 24 for Remote-Ready Models).
Equipment
Shutoff
Valve
Figure 18 - Equipment Shutoff Valve
104415-01M
Propane/LP
Supply Tank
Gas Meter
Figure 20 - Checking Gas Joints (Natural
Open
Closed
www.desatech.com
Equipment
Shutoff Valve
Thermostat Gas Valve or
Control Valve Location
Figure 19 - Checking Gas Joints
(Propane/LP Only)
Equipment Shutoff Valve
Gas Only)
17