LD1
OPTIMUM PROTECTION
for dwellings where occupants may be at high risk (e.g. elderly)
Optimum Protection LD1: As LD2, but in addition
Smoke or Heat Alarms should be located in all rooms
and other areas of the dwelling.
(apart from toilets or bathroom)
Smoke Alarms located:
on each storey
every 7.5 m of hallways and escape routes
within 3m of all bedroom doors
in all other rooms & areas other than listed below
(apart from toilets & bathrooms
Heat Alarms located in:
each Kitchen
garages
(Heat Alarms must be within 5.3m of potential fire
sources)
Smoke or Heat Alarms located in:
each Living room (i.e. most frequently used
daytime room)
Bedroom
Bedroom
Living
Room
Bedroom
Bedroom

Single Storey Dwelling LD1

Ionisation or Optical
Smoke Alarm
Heat Alarm
Shower
Bathroom
Kitchen

Multi Storey Dwelling LD1

Bathroom
Bedroom
7
)
Garage
Kitchen / Dining Room
Living Room
Optical Smoke Alarm
do not fit alarm