Fujitsu ASYG14LECA Installation Manual page 15

Indoor unit compact wall mounted type
Hide thumbs Also See for ASYG14LECA:
Table of Contents

Advertisement

2.4. Electric requirement
• Electric wire size and fuse capacity:
MODEL
2
Power supply cord (mm
)
2
Connection cord (mm
)
Fuse capacity (A)
• Use conformed cable with Type245 IEC57.
• Install all electrical works in accordance to the national standard.
• Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the
units. (Both indoor unit and outdoor unit)
• Install the circuit breaker nearby the units.
2.5. Accessories
Drain pipe
2.6. Additional charge
Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.
Pipe length
15 m
Additional refrigerant
None
When adding refrigerant, add the refrigerant from the charging port at the completion
of work.
The maximum length of the piping is 20 m. If the units are further apart than this, correct
operation can not be guaranteed.
Between 15 m and 20 m, when using a connection pipe other than that in the table, charge
additional refrigerant with 20 g/1 m as the criteria.
3. SELECTING THE MOUNTING POSITION
• Decide the mounting position with the customer as follows:
• Do not set to a place where there is oily smoke, oil is used in the factory, the unit can
contact sea breeze, sul de gases will be generated in the hot spring area, corrosive
gases will be generated, animal may urine on the unit and ammonia will be generated
and a dusty place.
3.1. Outdoor unit
(1) If possible, do not install the unit where it will be exposed to direct sunlight.
(If necessary, Install a blind that does not interfere with the air ow.)
(2) Do not install the unit where a strong wind blows or where it is very dusty.
(3) Do not install the unit where people pass.
(4) Take you neighbors into consideration so that they are not disturbed by air blowing into their
windows or by noise.
(5) Provide the space shown in gure so that the air ow is not blocked. Also for ef cient
operation, leave open three of the four directions front, rear, and both sides.
(6) Install the unit where keep away more than 3m from the antenna of TV set and Radio.
(7) Outdoor unit should be set to a place where both drainage and itself will not be
affected when heating.
Install at a place that can withstand the weight of the outdoor units and install positively
so that the units will not topple or fall.
Do not install where there is the danger of combustible gas leakage.
Do not install near heat sources.
In places where the outdoor temperature drops to 0 C or lower, the drain water may
freeze and may stop up the drain or cause other outdoor unit trouble. Therefore take
measures so that the drain water will not freeze and clog the drain.
In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with
snow, it might become dif cult to get warm and it is likely to cause of the breakdown.
Please construct a canopy and a pedestal or place the unit on a high stand (local
con gured).
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
12,000 ~ 14,000 BTU class
1.5
1.5 or 1
15
1
20 m
Rate
+100 g
20 g/m
CAUTION
WARNING
CAUTION
4. INSTALLATION DIAGRAM
Connection Cord
Conform to Type245 IEC57
[OUTDOOR UNIT]
60 cm or over
10 cm or over
20 cm or over
Outdoor unit
bottom
Drain pipe
Drain hose
When the outdoor temperature is 0 C or less, do not use the accessory drain pipe
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may
freeze in extreme cold weather. (Reverse cycle model only)
In the area with heavy snowfall, if the intake and outlet of outdoor units blocked with
snow, it might become dif cult to get warm and it is likely to cause of the breakdown.
Please construct a canopy and a pedestal or place the unit on a high stand (local
con gured).
5. INSTALLATION
5.1. Outdoor unit installation
Set the unit on a strong stand such as thing made of concrete blocks to minimize shock
and vibration.
Do not set the unit directly on the ground because it will cause trouble.
Switch cover A, B removal
(1) Remove the three tapping screws.
Hook
(2) Push downward the Switch cover B.
(3) Push upward the Switch cover A.
Switch cover A
Installing the Switch cover A, B
(1) After inserting the three hooks of Switch cover A,
then push upward, and then tighten the two tap-
Switch cover B
ping screws.
(2) After inserting the three hooks of Switch cover B,
Hooks
then push upward, and then tighten the one tap-
ping screw.
Hooks
Install the unit where it will not be tilted by more than 5°.
When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
INDOOR UNIT
10 cm or over
5 cm or over
• Do not directly install it on the
ground, otherwise it will cause
failure.
• To obtain better operation ef-
ficiency, when the outdoor unit
is installed, be sure to open the
front and left side.
54 cm
CAUTION
WARNING
25 cm or
over
En-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aoyg14lecAsyg12lecaAoyg12lecAsyg09leca

Table of Contents