DESIGN & TECHNICAL MANUAL
INDOOR
ASYG09KMCDN
ASYG12KMCDN
ASYG14KMCDN
OUTDOOR
AOYG09KMCDN
For Extra Cold Climate Area
AOYG12KMCDN
AOYG14KMCDN
DR_AS130EF_03
2021.03.10

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ASYG12KMCDN

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASYG09KMCDN ASYG12KMCDN ASYG14KMCDN OUTDOOR AOYG09KMCDN AOYG12KMCDN AOYG14KMCDN DR_AS130EF_03 2021.03.10...
  • Page 2 • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google Inc. ®...
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Dimensions....................4 2-1. Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN .......4 3. Wiring diagrams ....................6 3-1. Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN .......6 4. Capacity table....................7 4-1. Cooling capacity.......................7 4-2. Heating capacity ......................8 5. Fan performance ...................9 5-1.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............41 1. Specifications....................42 2. Dimensions....................43 2-1. Model: AOYG09KMCDN....................43 2-2. Model: AOYG12KMCDN....................44 2-3. Model: AOYG14KMCDN....................45 3. Installation space ..................46 3-1. Models: AOYG09KMCDN, AOYG12KMCDN, and AOYG14KMCDN ......46 4. Refrigerant circuit ..................49 4-1. Models: AOYG09KMCDN and AOYG12KMCDN ............49 4-2.
  • Page 5: Part 1. Indoor Unit

    Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASYG09KMCDN ASYG12KMCDN ASYG14KMCDN...
  • Page 6: Specifications

    1. Specifications Wall mounted Type Inverter heat pump Model name ASYG09KMCDN ASYG12KMCDN ASYG14KMCDN Power supply 230 V ~ 50 Hz Available voltage range 198—264 V 2.50 3.40 4.20 Rated Btu/h 8,500 11,600 14,300 Cooling 1.0—3.8 1.0—4.2 1.2—4.65 Min.—Max. Btu/h 3,400—13,000 3,400—14,300...
  • Page 7 Specifications for Lot10 Model name ASYG09KMCDN ASYG12KMCDN ASYG14KMCDN Cooling Energy efficiency class Heating (Average) Cooling 2.5 (35 °C) 3.4 (35 °C) 4.2 (35 °C) Pdesign Heating (Average) 2.5 (-10 °C) 3.6 (-10 °C) 4.2 (-10 °C) SEER Cooling kWh/kWh SCOP...
  • Page 8: Dimensions

    2. Dimensions 2-1. Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 4 - 2-1. Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN 2. Dimensions...
  • Page 9 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more The flare connection part should be installed outdoors. - 5 - 2-1. Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN 2. Dimensions...
  • Page 10: Wiring Diagrams

    3. Wiring diagrams 3-1. Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN - 6 - 3-1. Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN 3. Wiring diagrams...
  • Page 11: Capacity Table

    2.04 1.61 0.50 2.11 1.75 0.50 2.25 1.76 0.51 2.32 1.90 0.51 2.46 1.89 0.51 2.60 2.01 0.52 ¢ Model: ASYG12KMCDN Indoor temperature °CDB °CWB °CDB 2.50 2.08 0.41 2.78 2.09 0.41 2.88 2.28 0.41 3.07 2.28 0.42 3.16 2.46 0.42...
  • Page 12: Heating Capacity

    4-2. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG09KMCDN Indoor temperature °CDB °CWB 2.91 1.55 2.84 1.58 2.77 1.62 2.70 1.65 2.63 1.68 3.24 1.66 3.16 1.70 3.09 1.73 3.01 1.77 2.93 1.80...
  • Page 13: Fan Performance

    5. Fan performance 5-1. Air velocity distributions ¢ Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
  • Page 14: Airflow

    5-2. Airflow ¢ Model: ASYG09KMCDN  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 10 - 5-2. Airflow 5. Fan performance...
  • Page 15 ¢ Model: ASYG12KMCDN  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 11 - 5-2. Airflow 5. Fan performance...
  • Page 16 ¢ Model: ASYG14KMCDN  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 12 - 5-2. Airflow 5. Fan performance...
  • Page 17: Operation Noise (Sound Pressure)

    NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz ¢ Model: ASYG12KMCDN  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH NC-50 NC-50 HIGH NC-45...
  • Page 18 ¢ Model: ASYG14KMCDN  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH NC-50 NC-50 HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 19: Sound Level Check Point

    6-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 15 - 6-2. Sound level check point 6. Operation noise (sound pressure)
  • Page 20: Safety Devices

    7. Safety devices Model Type of Protection form protection ASYG09KMCDN ASYG12KMCDN ASYG14KMCDN Circuit Current fuse (PCB*) 250 V, 3.15 A protection °C Activate Fan motor stop Fan motor Thermal protection protection °C Reset Fan motor restart *PCB: Printed Circuit Board - 16 - 7.
  • Page 21: External Input And Output

    8. External input and output External input and output PCB SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 To CN6 on Indoor unit PCB External input External output Connector Input select Input signal Operation/Stop CN313/ Edge/Pulse Dry contact/ CN314 Forced stop —...
  • Page 22: External Input

    8-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 23: External Output

    8-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ External input and output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 24: Combination Of External Input And Output

    8-3. Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Mode...
  • Page 25: Details Of Function

    8-4. Details of function ¢ Control input function • When function setting is “Operation/Stop” mode 1 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Operation External input and 46-00...
  • Page 26 • When function setting is “Forced stop” mode – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Forced stop External input and 46-02 CN313 output PCB On →...
  • Page 27 • When function setting is “Operation/Stop” mode 2 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Operation External input and 46-03 CN313 Stop (R.C. output PCB On →...
  • Page 28 • Forced thermostat off function Rotary SW on External External input Input signal Command input and output PCB Off → On Thermostat off External input and output PCB CN313 On → Off Normal operation Input Compressor Room temp. Set temp. - 24 - 8-4.
  • Page 29 ¢ Control output function • Operation/Stop status Rotary SW on External Output External output Command input and output PCB signal Off → On Operation External input and output PCB CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 30: Group Connection

    9. Group connection NOTE: Group control cannot be used together with Wireless LAN adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 31: Remote Controller

    10. Remote controller 10-1. Wireless remote controller ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button...
  • Page 32 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 33: Function Settings

    11. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 11-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 34 NOTES: • The air conditioner custom code is set to prior to shipment. • If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner. - 30 - 11-1.
  • Page 35 ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function no. Functions Remote controller address setting Filter sign...
  • Page 36 2) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
  • Page 37 4) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 38 7) Cold air prevention This setting is to disable the cold air prevention function during heating operation. When disabled, the fan setting will always follow the setting on the remote controller. (Excluding defrost mode) Function number Setting value Setting description Factory setting Enable ♦...
  • Page 39 11) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. Function number Setting value Setting description Factory setting Disable Enable Remote controller...
  • Page 40: 11-2.Custom Code Setting For Wireless Remote Controller

    11-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 41: Accessories

    Part name Exterior Q’ty Operating manual Tapping screw (large) Installation manual Tapping screw (small) Wall hook bracket Cloth tape Remote controller Filter holder Remote controller Air cleaning filters holder Battery - 37 - 12-1. Models: ASYG09KMCDN, ASYG12KMCDN, and ASYG14KMCDN 12. Accessories...
  • Page 42: Optional Parts

    13. Optional parts 13-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wired remote UTY-RNRYZ* Wire type: Non-polar 2-wire controller Optional communication kit is necessary for installation. High visibility and easy operation.
  • Page 43 Exterior Part name Model name Summary Communication Use to connect Non-polar 2-core wired UTY-TWRXZ2 remote controller. For connection between indoor unit Modbus UTY-VMSX with UART interface and a Modbus converter open network. For connection between indoor unit KNX converter UTY-VKSX with UART interface and a KNX open network.
  • Page 44 - 40 - 13-2. Others 13. Optional parts...
  • Page 45: Part 2. Outdoor Unit

    Part 2. OUTDOOR UNIT SINGLE TYPE: AOYG09KMCDN AOYG12KMCDN AOYG14KMCDN...
  • Page 46: Specifications

    1. Specifications Type Inverter heat pump Model name AOYG09KMCDN AOYG12KMCDN AOYG14KMCDN Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Starting current Cooling 1,770 2,210 2,450 Airflow rate Heating 1,313 1,335 2,330 Type × Q'ty Propeller fan × 1 Motor output Cooling Sound pressure level *1...
  • Page 47: Dimensions

    2. Dimensions 2-1. Model: AOYG09KMCDN Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 43 - 2-1. Model: AOYG09KMCDN 2. Dimensions...
  • Page 48: Model: Aoyg12Kmcdn

    2-2. Model: AOYG12KMCDN Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 44 - 2-2. Model: AOYG12KMCDN 2. Dimensions...
  • Page 49: Model: Aoyg14Kmcdn

    2-3. Model: AOYG14KMCDN Unit: mm 4-M10 hole Pitch of bolts for installation Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 45 - 2-3. Model: AOYG14KMCDN 2. Dimensions...
  • Page 50: Installation Space

    3. Installation space 3-1. Models: AOYG09KMCDN, AOYG12KMCDN, and AOYG14KMCDN ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 51  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 52  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 53: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Models: AOYG09KMCDN and AOYG12KMCDN Heat exchanger 3-way ( INDOOR ) valve 2-way Muffler valve Muffler 4-way valve Strainer Expansion valve Heat exchanger Strainer ( OUTDOOR ) Cooling Heating :Thermistor (Discharge temp.) :Thermistor (Outdoor temp.) :Thermistor (Heat exchanger out temp.) :Thermistor (Room temp.) :Thermistor (Pipe temp.) - 49 -...
  • Page 54: Model: Aoyg14Kmcdn

    4-2. Model: AOYG14KMCDN Heat exchanger 3-way (INDOOR) valve 2-way Muffler valve Muffler Pressure switch Strainer 4-way valve Expansion valve Accumulator Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Compressor temperature) : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Room temperature) : Thermistor (Pipe temperature) - 50 -...
  • Page 55: Wiring Diagrams

    5. Wiring diagrams 5-1. Models: AOYG09KMCDN and AOYG12KMCDN - 51 - 5-1. Models: AOYG09KMCDN and AOYG12KMCDN 5. Wiring diagrams...
  • Page 56: Model: Aoyg14Kmcdn

    5-2. Model: AOYG14KMCDN - 52 - 5-2. Model: AOYG14KMCDN 5. Wiring diagrams...
  • Page 57: Capacity Compensation Rate For Pipe Length And Height Difference

    6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Model: AOYG09KMCDN NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 58: Model: Aoyg12Kmcdn

    6-2. Model: AOYG12KMCDN NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — 0.939 0.925 — — 0.966 0.947 0.932 Indoor unit is higher than outdoor unit *1 — 0.979 0.970 0.951 0.936...
  • Page 59: Additional Charge Calculation

    7. Additional charge calculation 7-1. Model: AOYG09KMCDN Refrigerant type Refrigerant amount Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge 7-2. Model: AOYG12KMCDN Refrigerant type Refrigerant amount Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge...
  • Page 60: Airflow

    8. Airflow 8-1. Model: AOYG09KMCDN  Cooling 1,770 1,042  Heating 1,313 8-2. Model: AOYG12KMCDN  Cooling 2,210 1,301  Heating 1,335 8-3. Model: AOYG14KMCDN  Cooling 2,450 1,442  Heating 2,330 1,371 - 56 - 8-1. Model: AOYG09KMCDN 8. Airflow...
  • Page 61: Operation Noise (Sound Pressure)

    9. Operation noise (sound pressure) 9-1. Noise level curve ¢ Model: AOYG09KMCDN  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 62: Sound Level Check Point

    ¢ Model: AOYG14KMCDN  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz 9-2.
  • Page 63: Electrical Characteristics

    10. Electrical characteristics Model name AOYG09KMCDN AOYG12KMCDN AOYG14KMCDN Voltage 230 ~ Power supply Frequency Max operating current *1 11.5 16.0 Starting current Circuit breaker current Power cable Cross- Wiring sectional spec. *2 area Connection cable *3 Limited wiring length *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 64: Safety Devices

    11. Safety devices Model Type of protection Protection form AOYG09KMCDN AOYG12KMCDN AOYG14KMCDN 250 V, 25 A Circuit protection Current fuse (Main PCB) 250 V, 5 A 103±18 °C 125±10 °C Activate Fan motor stop Fan motor stop Fan motor Thermal protection protection 95±18 °C 120±10 °C...
  • Page 65: Accessories

    12. Accessories 12-1. Models: AOYG09KMCDN, AOYG12KMCDN, and AOYG14KMCDN Part name Exterior Q’ty Part name Exterior Q’ty Installation manual - 61 - 12-1. Models: AOYG09KMCDN, AOYG12KMCDN, and AOYG14KMCDN 12. Accessories...