4.5 Condensate Connections

Provision must be made for removal of condensate from the boiler and flue system.
Condense is mildly acidic, typically pH3 - pH5.
Condense pipework must be non-corrosive and not copper. Hamworthy recommend
32mm dia. Plastic waste pipe.
Condense may be discharged to a standard drain subject to National or Local
regulations.
Location of condense pipework should prevent freezing within tundishes, traps and
pipework.
The connection to the boiler condense drain accepts a straight push-fit coupling for
32mm i.d. plastic waste pipe.
Figure 4.5.1 - Boiler Condensate Connection
Boiler Condensate
Connection
(32mm o/d)
Figure 4.5.2 – Boiler Condensate Connection
HAMWORTHY HEATING LTD
9
WESSEX MODUMAX 100 SERIES
The vo lume of con den sa te
is r ela ted to the syste m w ater
tempe rat ure an d fi ring ra te
of b oil er.
Boi ler Flu e
Con dense 'U' Tr ap
Open Tu ndi sh
Me tal she ath to pr otect
plastic pi pe
Minimum Fa ll 30 mm/m
(1 in 30)
500001123/C