Coding Addresses
Switching Module-V
Function
Boiler water temperature
setpoint (pool, spa,
snowmelting applications)
Party mode
Time limit for party mode
(continued)
Factory default setting
Address: Value
32 : 70 Minimum boiler water temperature
setpoint value 158ºF/70ºC with
external heat demand signal
F2 : 0
No time limit for party mode
Quick Reference Guide
Possible change
Address: Value
32 : 0
Minimum boiler water temperature
to
setpoint value variable between 32
32: 127
and 26ºF/0 and 127ºC;
note adjustment of adjustable high
limit
.
F2 : 1
Time limit for party mode between one
to
and twelve hours
F2: 12