Burglary Zone Wiring
TM
NAPCO's EZ Zone Doubling
terminal has 2 zones, use an E (2.2 K) type Zone
Doubling Resistor for the primary zone and a Z
(3.9 K) type Zone Doubling Resistor for the
secondary zone.
Terminals
Primary
3&4
Zone 1
5&4
Zone 2
6&7
Zone 3
TABLE
2 EZ Z
D
TM
ONE
OUBLING
Wire zones as shown in the wiring diagram (pg.
27). All resistors must be installed, even if the
zone is not used. If required, unsupervised open
circuit devices may be used instead of closed
circuit devices. Program the zone as an Open
Circuit Zone [06] (Zone Doubling Resistor re-
quired).
If necessary, use the voltage chart
below to verify proper voltages.
Primary and Secondary zones normal
Secondary open
Primary open
Primary and Secondary open
Primary and Secondary shorted (Sys. Trbl 7-
Zone Trbl)
TABLE
3 V
T
OLTAGE AT
ERMINALS
Fire Zone Wiring
Wire the Fire Zone as shown in the Wiring
Diagram in the back of this manual. An EOL
is simple. Each
resistor must be installed, even if the Fire Zone
is not used.
Fire Zone Normal
Fire Trouble
Secondary
Fire
Zone 4
TABLE
4 V
Zone 5
Zone 6
PGM Wiring
The PGM is a switched negative output that is
activated depending on the programming op-
tion(s) that have been selected [08], [23] - [25].
Connect the device controlled by the PGM
between +PWR and the PGM terminal
(maximum load of 50 mA).
.H\SDG 2SHUDWLRQ
1.9 V
Keypad zone LEDs indicate zone status.
2.5 V
ARMED, STATUS and
3.2 V
vide system status. The keypad sounder pro-
vides feedback beeps for correct and incorrect
5.0 V
entries.
0.0 V
3&4, 5&4, 6&7
13.0V
13.8V
0.0 V
F
Z
(Terminals 8&9)
OLTAGE AT
IRE
ONE

SYSTEM LEDs pro-
Keypad Sounder
3
QUICK BEEPS
Panel Armed (System ON)
Chime ON
Fault Find Mode ON
Keypad Sounder ON
Zone Bypassed
6
QUICK BEEPS
Panel Disarmed (System OFF)
Chime OFF
Fault Find Mode OFF
Keypad Sounder OFF
Zone Un-Bypassed
1
-
SECOND
STEADY TONE
Incorrect Code Entered
Invalid key entry
4
(
LONG BEEPS
PRIORITY CONDITION
1. Entering an Arm Code with a faulted zone
(Not an Auto-Bypass Reentry Zone).
 
2. Entering an Arm Code when the Bell or
PGM is ON (Bell and PGM will turn OFF).
3. Arming with the Fire LED ON - reset re-
quired. Press the
key.
)
7