5. Defrost operation control
(1) Starting the defrost operation
• Defrost operation is started when the pipe temperature (TH5) of -10˚C or below (-8˚C or below for P400-
type and above) has continuously been detected for 3 minutes after the integrated compressor operation
time of 50 minutes have passed.
• If 10 minutes have passed since compressor start-up or since the completion of defrost operation, forced
defrost operation will start by turning on the forced defrost switch (DIPSW2-7).
• Even if the defrost prohibit timer is set to 90 minutes, the actual defrost prohibit time for the next operation
will be 50 minutes if defrosting took 12 minutes.
(2) Defrost operation
Compressor frequency
Outdoor unit fan
SV1
SV2
SV3 (P450-P650 types only)
21S4a
21S4b (P400-P650 types only)
BC controller LEV12
BC controller LEV34
BC controller LEV3a
BC controller SVM1
BC controller SVM2
(3) Completion of defrost operation
• Defrost operation will stop when 12 minutes have past since the beginning of defrost operation or when the
piping temperature (TH5) of 10˚C or above has been continuously detected for 2 minutes. (TH5 above 7˚C for
2 minitues for P400 models and above)
• Defrost operation will not stop its operation for 2 minutes once started unless the piping temperature
exceeds 25˚C within 2 minutes, in which case the operation will stop.
(Above 20˚C within 2 minitues for P400 type models and above)
(4) Problems during defrost operation
• If a problem is detected during defrost operation, the operation will be stopped, and the defrost prohibition
time based on the integrated compressor operation time will be set to 20 minutes.
(5) Change in the number of operating indoor units during defrost operation
• Even when there is a change in the number of operating indoor units during defrost operation, the operation
will continue, and an adjustment will be made after the completion of the defrost operation.
• Defrost operation will be continued, even if the indoor units stop or if thermo is turned off, until it has run its
course.
Model
No.1 Compressor
P200 type
P250 type
P300 type
P350 type
P400 type
P450 type (50/60Hz)
110/100
P500 type (50/60Hz)
110/100
P550 type (50/60Hz)
110/100
P600 type (50/60Hz)
110/100
P650 type (50/60Hz)
110/100
Stopped
G-type : 4000, GA-type : 6000
G-type : 1000, GA-type : 2000
60 (fully closed)
- 94 -
No. 2 Compressor
72
65
65
65
114
ON (50/60Hz)
ON (50/60Hz)
ON (50/60Hz)
ON (50/60Hz)
ON (50/60Hz)
ON
ON
ON
OFF
OFF
ON
OFF