11. Operation mode
(1) Indoor unit operation modes
An operation mode can be selected from the following 5 modes on the remote controller.
1
Cooling mode
2
Heating mode
3
Dry mode
4
Fan mode
5
Stopping mode
(2) Outdoor unit operation modes
Five operation modes of the outdoor units
1
Cooling only
2
Heating only
3
Cooling main
4
Heating main
5
Stopping mode
When the indoor units are in the combination of cooling and heating modes, operation mode
(cooling main or heating main mode) is determined by the outdoor unit based on the refrigerant
pressure and variation rate in the R2 refrigerant circuit.
(3) Patterns of the auto cooling-heating changeover operation
When the auto heating-cooling changeover mode is selected, indoor temperature is detected as shown in the operation
pattern shown below, and the cooling or heating mode is automatically selected.
1.5K
1K
Cooling mode
1.5K
1K
(4) Relationships between operation modes and load capacity (kW) (within the same refrigerant system)
Cooling load
capacity
Cooling load
Heating load
+
capacity
capacity
All indoor units in are in cooling mode.
All indoor units in are in heating mode.
Indoor units in the combination of cooling and heating modes
Indoor units in the combination of cooling and heating modes
All indoor units are in fan or stopping mode
Fan mode
Heating mode
100(%)
Cooling load
X100=Cooling
load (%)
0
Cooling-only
Cooling-main
mode
mode
Total heat recovery mode
- 99 -
Fan mode
0
Heating load
Heating
load (%)
100(%)
Heating-main
Heating-only
mode
mode
Switches to cooling mode
Cooling with thermo on
Set temperature
( To[changeable between
19 and 28˚C] )
Heating with thermo ON
Switches to heating mode
Heating load
capacity
=
X100
Cooling load
Heating load
+
capacity
capacity

Hide quick links: