Mitsubishi Electric PURY-P200 Service Handbook page 139

City multi r410a
Table of Contents

Advertisement

Checking code
Meaning, detecting method
High pressure
5201
1. When pressue sensor detects
sensor
0.098MPa or less during
abnormality
operation, outdoor unit once
(outdoor unit)
stops with 3 minutes
restarting mode, and restarts
if the detected pressure of
pressure sensor ex-ceeds
0.098MPa imediately before
restarting.
2. If the detected pressure of
sensor is less than 0.098MPa
immediately before restarting,
error stop is commenced
displaying 5201.
3. Under 3 minutes restarting
mode, LED displays
intermittent fault check.
4. During 3 minutes after
compressor start, defrosting
and 3 minutes after defrosting
operations, trouble detection
is ignored.
5201
Liquid
When pressure sensor detects
side
4.06MPa or more, error code
"5201" or "5203" is displayed.
However, error stop is not made,
and backup operation will starts.
5203
Inter-
mediate
5301
ACCT sensor
-1.5Arms
5305
abnormality
effective value
(Error details
detected during inverter
No.115)
operation.
DCCT sensor
An abnormal value is detected
abnormality
in the DCCT detection circuit
(Error details
just before the INV started.
No.118)
Other than
P200 model
An abnormal value was
ACCT
detected with the ACCT
sensor/circuit
detection circuit just before the
abnormality
INV started.
(Error details
No.117)
For the check code on the inverter, refer to
(1) Pressure sensor trouble.
(2) Inner pressure drop due to
a leakage.
(3) Broken cover.
(4) Coming off of pin at
connector portion, poor
contact.
(5) Broken wire.
(6) Faulty thermistor input circuit
of MAIN board.
(1) Pressure sensor trouble.
(2) Inner pressure drop due to
a leakage.
(3) Broken cover.
(4) Coming off of pin at
connector portion, poor
contact.
(5) Broken wire.
(6) Faulty thermistor input circuit
of MAIN board.
output current's
(1) Contact is faulty.
1.5Arms was
(2) ACCT sensor is faulty.
(1) Contact is faulty.
(2) DCCT sensor incorrectly
installed.
(3) DCCT sensor is faulty.
(4) INV board fault.
(1) INV board fault.
(2) Compressor ground fault
and IPM fault.
"
7. Inverter and compressor
- 136 -
Cause
Checking method & Countermeasure
See Troubleshooting of
pressure sensor.
See Troubleshooting of
pressure sensor.
Check the INV board CNCT2
(ACCT) contact, CNDR2 and
G/A Board CNDR1.
Replace the ACCT sensor
Check the connector connection
on the INV board CNCT (DCCT),
DCCT side.
Check DCCT installation
direction
Replace the DCCT sensor
Replace the INV board
Refer to 9.[4].7.(2).[1]
"Check the INV board error
detection circuit"
Refer to 9.[4].7.(2).[2]
"Check for com-pressor ground
fault or coil error."
Refer to 9.[4].7.(2).[5]
"Check the inverter circuit trouble".
"
"
in the section [4]
Troubleshooting of principal parts
"