Mitsubishi Electric PURY-P200 Service Handbook page 145

City multi r410a
Table of Contents

Advertisement

Checking
code
No ACK abnormality
6607
(continued)
System
Generating
Display of
com-
unit
trouble
position
address
4. Remote
Remote
controller
controller
(RC)
(RC)
Meaning, detecting method
When no ACK signal is detected in 6 continuous times with 30 seconds
interval by transmission side controller, the transmission side detects
error.
Note : The address/attribute shown on remote controller indicates the
controller not providing the answer (ACK).
Detecting
Cause
method
No reply
Same cause as that for plural re-
(ACK) at
frigerant system.
transmission
of IC to RC
No reply
Trouble of partial IC units:
(ACK) at
(1) Same cause of that for single
transmission
refrigerant system.
of MELANS
to RC
Trouble of all IC in one
refrigerant system:
(1) Error detected by OC unit.
Total capacity error. (7100)
Capacity code setting error.
(7101)
Connecting number error.
(7102)
Address setting error. (7105)
(2) Disconnection or short circuit
of transmission line of OC
unit terminal block for central
control (TB7).
(3) Power source shut down of
OC unit.
(4) Trouble of OC unit electrical
system.
Trouble of all IC:
(1) As same that for single
refrigerant system.
(2) When using the power
supply unit for transmission
line, the power supply
connector (CN40) is inserted
into the transmission line for
centralized control.
(3) Disconnection or power
shutdown of power supply
unit for transmission line.
(4) Faulty MELANS.
- 142 -
Cause checking method &
Countermeasure
Same countermeasure as that for
plural refrigerant system.
→ Same countermeasure as that for
single refrigerant system.
Confirm OC trouble diagnosis LED.
→ At trouble generation, check for the
content according to check code.
Check the content of (2) ~ (4) shown
left.
Check the causes of (1) ~ (4) left.

Hide quick links:

Advertisement

Table of Contents
loading