Setting of DIP SW5
220V
240V
ON : 220V
ON
OFF
OFF : 240V
(PLFY-P·VLMD-E)
Switch
Function
Ceiling height
SWA
setting
External static
SWA
pressure setting
Setting of air outlet
SWB
opening
SWC
Airflow control
230V
(PCFY-P-VGM-E)
Ceiling height
3
3
3.5m
2
2
2.8m
1
1
2.3m
(PDFY-P20 ~ 80VM-E, PEFY-P20 ~ 80VMM-E)
100Pa
3
50Pa
2
30Pa
1
For other models, change the setting of static pressure by replacing
the connector.
(PLFY-P-VAM-E)
2-way
3-way
4-way
(PLFY-P-VAM-E, PCFY-P-VGM-E, PKFY-P-VGM-E, PDFY-P-VM-E)
Option
Set to the option to install the high efficiency filter.
Standard
Operation by switch
SWB
1
2
SWA
4.0m
4.2m
2-way
(3.3m)
(3.5m)
3.6m
4.0m
3-way
(3.0m)
(3.3m)
3.2m
3.6m
4-way
(2.7m)
(3.0m)
Values in the parenthese are for
P32~80 types.
- 89 -
Switch set timing
Always after powering
Always after powering
3
4.2m
Always after powering
(3.5m)
4.2m
(3.5m)
Always after powering