Chapter 3: Programming
To program loop events:
1.
Press the Menu button.
2.
Choose Program.
3.
Choose Advanced Program.
4.
Enter the level two password.
5.
Choose Loop Events.
6.
Select the loop event.
7.
Choose Event Notification.
8.
Set the event notification. See default settings in the table
above.
Printer: Yes or No. Specifies if event information is printed
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET: Yes or No. Specifies if event information is sent to the
connected network
CID: Contact ID event code (000 to 999)
9.
When finished, choose Save.
10. Repeat steps 6 to 9 for each loop event.
11. Continue programming your system or press Menu to exit
menu mode.
152
Reports
Test
Control
Program
Program
Auto Program
Advanced Program
Date and Time
Enter Password
0000
Advanced Program
Panel Operation
Panel Events
Loop Events
Loop Events
Loop 1 Initializing
Loop 1 Fault
Loop 1 Map Fault
Loop 1 Initializing
Event Notification
Trouble
Printer
Dialer
Account 1&2
NET
Trouble
NET
CID
Save
Vigilant VS1 and VS2 Technical Reference Manual
Yes<>
Yes<>
Yes
110