GE Security Vigilant VS1 Technical Reference Manual page 160

Control panel
Hide thumbs Also See for Vigilant VS1:
Table of Contents

Advertisement

Chapter 3: Programming
7.
Choose Event Notification.
8.
Set the event notification. See the default settings in the table
above.
Printer: Yes or No. Specifies if event information is printed
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET: Yes or No. Specifies if event information is sent to the
connected network
CID: Contact ID event code (000 to 999)
9.
When finished, choose Save.
10. Repeat steps 6 to 9 for each panel event.
11. Continue programming your system or press Menu to exit
menu mode.
150
Enter Password
0000
Advanced Program
Panel Operation
Panel Events
Loop Events
Panel Events
System Startup
Ground Fault
Battery Charger
System Startup
Event Notification
Trouble
Printer
Dialer
Account 1&2
NET
Trouble
NET
CID
Save
Vigilant VS1 and VS2 Technical Reference Manual
Yes<>
Yes<>
Yes
110