Minimum Clearances; Venting - Bradford White PDX1-40S6FBN Installation And Operating Instruction Manual

Powered direct vent gas water heater
Table of Contents

Advertisement

Minimum Clearances

Failure to adhere to these installation and operating instructions
may create a hazard to life and property and will nullify the
warranty.
This installation must allow access to the front of the water heater and
adequate clearance must be provided for servicing and operating this water
heater. The water heater may be installed on either a combustible or non-
combustible floor. If the water heater is to be installed directly on carpeting, it
must be installed on top of a metal or wood panel extending beyond the full
width and depth of the appliance by at least three (3) inches (7.6 cm) in any
direction or, if the appliance is to be installed in an alcove or closet, the entire
floor must be covered by the panel. The minimum clearances to combustibles
for this water heater are: zero (0) inch (0 cm) from the sides and rear, five (5)
inches (12.7 cm) from the front of the jacket, zero (0) inch (0 cm) from the vent
connector and fifteen (15) inches (38.1 cm) from the jacket top. Increase
distances to provide clearance for servicing.

Venting

Figure 1 – Direct Vent Terminal Clearances
WARNING
8