Minimum Clearances

Failure to adhere to these installation and operating
instructions may create a hazard to life and property and will
nullify the warranty.
This installation must allow access to the front of the water heater and adequate
clearance must be provided for servicing and operating this water heater. The
water heater may be installed on either a combustible or non-combustible floor.
If the water heater is to be installed directly on carpeting, it must be installed on
top of a metal or wood panel extending beyond the full width and depth of the
appliance by at least 3 inches (7.6 cm) in any direction or, if the appliance is to
be installed in an alcove or closet, the entire floor must be covered by the panel.
The minimum clearances to combustibles for this water heater are: 0 inch from
the sides and rear, 5 inches (12.7 cm) from the front of the jacket, 0 inch from
the vent connector and 15 inches (38.1 cm) from the jacket top. Increase
distances to provide clearance for servicing.

Venting

WARNING
Figure 1 - Vent Terminal Clearances