York AFFINITY BHZ Technical Manual page 22

2 - 5 ton 60 hertz affinity series
Hide thumbs Also See for AFFINITY BHZ:
Table of Contents

Advertisement

718419-YTG-D-0613
BHZ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
Net
1
Capacity
WB
CFM
(MBh)
(°F)
77
52.2
72
47.9
1500
67
43.5
62
40.2
57
42.0
77
52.9
72
48.5
1750
67
44.1
62
40.7
57
42.6
77
53.6
72
49.2
2000
67
44.7
62
41.3
57
43.2
72
50.7
67
46.1
2250
62
42.6
57
44.6
72
52.3
67
47.5
2500
62
43.9
57
45.9
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
22
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
115°F
6.2
27.9
20.8
13.7
6.1
36.8
29.7
22.6
5.9
43.5
38.6
31.5
5.8
40.2
40.2
39.4
5.8
42.0
42.0
36.6
6.4
36.9
23.6
14.7
6.2
41.1
32.6
24.2
6.1
44.1
41.6
33.7
5.9
40.7
40.7
42.2
5.9
42.6
42.6
39.2
6.5
45.9
26.4
15.7
6.4
45.3
35.6
25.8
6.2
44.7
44.7
36.0
6.1
41.3
41.3
45.1
6.1
43.2
43.2
41.8
6.5
48.8
38.3
27.2
6.3
46.1
46.1
37.9
6.2
42.6
42.6
44.5
6.2
44.6
44.6
43.9
6.6
52.3
41.0
28.6
6.4
47.5
47.5
39.9
6.3
43.9
43.9
43.9
6.3
45.9
45.9
45.9
Temperature of Air on Condenser Coil
Net
1
Capacity
(MBh)
75
70
65
-
-
-
46.7
15.5
-
-
42.0
24.3
17.2
-
37.2
32.3
25.1
18.0
34.7
29.4
22.3
15.2
37.6
-
-
-
47.8
15.8
-
-
43.0
25.3
16.9
-
38.1
33.8
25.4
17.0
35.5
30.8
22.3
13.9
38.5
-
-
-
48.9
16.1
-
-
43.9
26.3
16.6
-
39.0
35.4
25.6
15.9
36.3
32.1
22.4
12.7
39.4
16.2
-
-
45.8
26.9
15.8
-
40.7
33.4
22.3
11.3
37.9
32.8
21.7
10.7
41.0
16.2
-
-
47.7
27.5
15.1
-
42.4
31.5
19.0
6.6
39.4
33.5
21.1
8.7
42.7
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
125°F
6.6
26.3
19.2
12.1
6.5
33.6
26.5
19.4
6.4
37.2
33.8
26.7
6.2
34.7
34.7
34.7
6.2
37.6
37.6
31.0
6.8
36.9
22.6
13.4
6.7
38.4
30.0
21.6
6.6
38.1
37.4
29.7
6.4
35.5
35.5
35.5
6.4
38.5
38.5
34.6
7.0
47.5
26.1
14.8
6.9
43.3
33.5
23.8
6.8
39.0
39.0
32.8
6.6
36.3
36.3
36.3
6.6
39.4
39.4
38.2
7.0
45.8
36.0
25.0
6.9
40.7
40.7
34.4
6.7
37.9
37.9
37.9
6.7
41.0
41.0
40.4
7.0
47.7
38.5
26.1
6.9
42.4
42.4
36.0
6.7
39.4
39.4
39.4
6.7
42.7
42.7
42.7
Johnson Controls Unitary Products
75
70
65
-
-
-
12.2
-
-
19.5
12.4
-
28.1
20.9
13.8
23.9
16.8
9.7
-
-
-
13.2
-
-
21.3
12.9
-
30.7
22.2
13.8
26.2
17.8
9.4
-
-
-
14.1
-
-
23.1
13.4
-
33.3
23.5
13.8
28.5
18.8
9.1
13.9
-
-
23.3
12.3
-
30.1
19.1
8.0
29.4
18.3
7.2
13.7
-
-
23.6
11.1
-
27.0
14.6
2.2
30.2
17.8
5.4

Hide quick links: