Operating Procedure - Mitsubishi Electric PUHZ-FRP71VHA Service Manual

Split-type, heat pump air conditioner
Hide thumbs Also See for PUHZ-FRP71VHA:
Table of Contents

Advertisement

OPERATING PROCEDURE

4. Removing the thermistor <Outdoor 2-phase pipe> (TH6)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Disconnect the connector TH7/6 (red) on the controller
circuit board in the electrical parts box.
(4) Disconnect the lead wires from the wire clip on the outdoor
controller board in the electrical parts box.
(5) Loosen the clamp for the lead wire in the rear of the
electrical parts box.
(6) Pull out the thermistor <Outdoor 2-phase pipe> (TH6) from
the sensor holder.
Note: When replacing thermistor <Outdoor 2-phase pipe>
(TH6), replace it together with thermistor <Outdoor>
(TH7), since they are combined together.
Refer to procedure No.5 below to remove thermistor
<Outdoor>.
5. Removing the thermistor <Outdoor> (TH7)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Disconnect the connector TH7/6 (red) on the controller
circuit board in the electrical parts box.
(4) Disconnect the lead wires from the wire clip on the outdoor
controller board in the electrical parts box.
(5) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See Photo 5)
(6) Pull out the thermistor <Outdoor> (TH7) from the sensor
holder.
Note: When replacing thermistor <Outdoor> (TH7), replace
it together with thermistor <Outdoor 2-phase pipe>
(TH6), since they are combined together.
Refer to procedure No.4 above to remove thermistor
<Outdoor 2-phase pipe>.
6. Removing the thermistor <Outdoor pipe> (TH3), thermistor
<Discharge> (TH4) and thermistor <Comp. surface> (TH34)
(1) Remove the service panel. (See Photo 1)
(2) Disconnect the connectors, TH3 (white) and TH4 (white),
TH34 (black) on the controller circuit board in the electrical
parts box.
(3) Disconnect the lead wires from the wire clip on the outdoor
controller board in the electrical parts box.
(4) Loosen the clamp for the lead wire in the rear of the
electrical parts box. (See Photo 5)
(5) Pull out the thermistor <Outdoor pipe> (TH3) and
thermistor <Discharge> (TH4) from the sensor holder.
[Removing the thermistor<Comp. surface> (TH34)]
(6) Remove the compressor cover (upper) and pull out the
thermistor <Comp. surface> (TH34) from the holder of the
compressor surface. (TH3, TH34 : See Figure 1)
OCH544
Photo 5
Electrical parts box
Controller
circuit board
(C.B.)
Photo 6
Lead wire of thermistor <Outdoor> (TH7)
Photo 7
Thermistor
(TH4)
<Dischage>
100
PHOTOS
Thermistor
<Outdoor 2-phase pipe>
(TH6)
Thermistor
Clamp
<Outdoor pipe>
(TH3)
Sensor holder
Thermistor
(TH34)
<Comp. surface>

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents