Mitsubishi Electric PUHZ-FRP71VHA Service Manual page 69

Split-type, heat pump air conditioner
Hide thumbs Also See for PUHZ-FRP71VHA:
Table of Contents

Advertisement

SW2 setting
LEV-A opening pulse on error occuring
0 – 480
ON
1
2 3 4 5 6
Indoor room temperature (TH1) on error
ON
occurring
8 – 39
1
2 3 4 5 6
Indoor pipe temperature / Liquid (TH2)
on error occurring
-39 – 88
ON
1
2 3 4 5 6
Indoor pipe temperature / Cond./ Eva.
(TH5) on error occurring
ON
-39 – 88
1
2 3 4 5 6
Outdoor pressure sensor saturated tem-
perature (63HS) on error occurring
-39 – 88
ON
1
2 3 4 5 6
Outdoor temperature (TH7) on error
occurring
-39 – 88
ON
1
2 3 4 5 6
Outdoor heatsink temperature (TH8) on
error occurring
ON
-40 – 200
1
2 3 4 5 6
Discharge superheat on error occurring
SHd
ON
0 – 255
1
2 3 4 5 6
TH4 - 63HS
Sub cool on error occurring SC
0 – 130
ON
1
2 3 4 5 6
OCH544
Display detail
69
The black square ( ) indicates a switch position.
Explanation for display
0 – 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs.
8 – 39
-39 – 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-39 – 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-39 – 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-39 – 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs.
-40 – 200
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
0 – 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs.
0 – 130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 secs.
0.5secs.
2 secs.
1
30
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
15
0.5secs.
2 secs.
1
50
0.5secs.
2 secs.
1
15
Unit
Pulse
:
:
:
:
:
:
:
: