Differential Pressure Switch Settings; Vs3000 Water Temperature Sensor - Resistance Vs Temperature - Burnham Revolution Installation, Operating And Service Instructions

Gas- fired boiler
Hide thumbs Also See for Revolution:
Table of Contents

Advertisement

NOTE: If switch drops-out before boiler reaches
temperature or if pressure differential readings are
below minimums shown in Table 12, check for
cracks in hose or contact your nearest Burnham
representative.
4. Stop boiler, remove manometer and reconnect hoses
to differential pressure switch. See Figures 51 and
54.
H.
VS3000 / VS3001 Water Temperature Sensor Testing
Instructions
A good quality test meter capable of measuring up to
50k ohms (1k ohm = 1000 ohms) is required to measure
the sensor resistance. In addition to this, the actual
temperature must be measured with either a good
quality digital thermometer, or if a thermometer is not
available, a second sensor can be placed alongside the
one to be tested and the readings compared.
Table 1: Differential Pressure Switch Settings
Boiler Model
RV3
RV4
RV5
RV6
RV7 (1" Burners)
RV7 (40mm Burners)
Table 13: VS3000 Water Temperature Sensor - Resistance vs Temperature
°F
OHMS
50
19,900
15,000
60
70
11,900
100
Sea Level to 2,000 Ft.
.40" w.c.
.88" w.c.
.80" w.c.
.80" w.c.
.69" w.c.
.74" w.c.
°F
°F
OHMS
9,170
80
110
7,400
120
90
5,780
130
First measure the temperature using the thermometer
and then measure the resistance of the sensor at the
control. The wires from the sensor must not be
connected to the control while the test is performed.
Using Table 13, estimate the temperature measured by
the sensor. The sensor and thermometer readings
should be close. If the test meter reads a very high
resistance, there may be a broken wire, a poor wiring
connection or a defective sensor. If the resistance is
very low, the wiring may be shorted, there may be
moisture in the sensor or the sensor may be defective.
To test for a defective sensor, measure the resistance
directly at the sensor location.
Do not apply voltage to a sensor at any time as
damage to the sensor may result.
Minimum Differential Pressure
°F
OHMS
OHMS
4,730
2,490
140
3,740
150
2,010
3,100
1,700
160
Above 2,000 Ft. Elevation
.25" w.c.
.74" w.c.
.65" w.c.
.65" w.c.
.54" w.c.
.59" w.c.
°F
°F
OHMS
170
1,390
200
210
180
1,180
977
220
190
OHMS
838
701
606
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents