Radiant Tube Assembly - Brant Radiant Heaters DES3-20-50 Owner's Manual

Des3 series gas-fired infrared tube heater
Hide thumbs Also See for DES3-20-50:
Table of Contents

Advertisement

3.0
Installation

Radiant Tube Assembly

Radiant Tube Assembly
To install the radiant tubes:
Place tubes in hangers with the welded seam facing downward and the swaged end of the tube
1
towards the exhaust end of the heater system (see figure 3.6).
Refer to page 23 for tube installation sequence. Place the combustion chamber as the first tube
connected to the burner control box. Models 150-200 MBH utilize a titanium combustion chamber with
yellow identification tag.
Figure 3.6
Attach Hangers
Hanger
Slide tube clamps onto radiant tubes (see figure 3.7)
2
Figure 3.7
Attach Tube Clamps
Concave surface
Radiant Tube
Welded Seam
Faces Down
NOTE: If the tube clamp comes
apart, the spacer must be
re-assembled with the spacer's
concave surface facing against
the radiant tube surface.
IMPORTANT! 150,000 to 200,000 BTU/h models must be installed
with a stainless steel tube clamp (P/N: TP-220) located at the seam
between the primary combustion chamber and the second tube
section downstream of the burner control box.
16
DES3
Series
Swaged End
Tube Clamp

Advertisement

Table of Contents
loading