3.0
Installation

Combustion Air Requirements

Vertical Outside Air Supply for Common Intake
Figure 3.24
NOTE: Common intake
heaters must share the
same thermostat.
Burner
Control Box
Combustion Air Requirements
Combustion air may be supplied to the heater by indoor or outdoor means. Follow these guidelines and all
applicable codes for all models prior to installing the combustion air duct work. Local codes may vary. In
the absence of local codes, refer and comply with the National Fuel Code ANSI Z223.1 (NFPA 54) latest
edition or the National Standards of Canada.
Sufficient combustion air must be supplied to the appliance at all times.
Lack of combustion air may result in property damage, serious injury or death.
This unit comes standard equipped for connection of supplied outdoor air for combustion. It is designed
for outside air to be brought into the appliance from combustion intake ducts, and is referred to as a
"Separated Combustion" appliance.
This heater must operate as a separated combustion system if any of the following criteria apply:
• Chemicals such as chlorinated or fluorinated hydrocarbons (typical sources are refrigerants,
solvents, adhesives, degreasers, paints, paint removers, lubricants, pesticides, etc.) are present in
the atmosphere.
• High humidity.
• Contaminants such as sawdust, welding smoke, etc.
• Negative building pressure.
• Unusually tight construction where the air infiltration rate is less than 0.40 air changes per hour.
If your application does not meet any of these criteria, then room air may be used as supplying
combustion air to the heater. Refer to 'Combustion Air Supply - Room Air' on page 34 for details on how to
utilize room air for combustion.
18 in.
minimum
Air Inlet Connection
4" intake pipe
WARNING
!
Side View
Roof Intake Cap
6" pipe
Air Inlet Connection
4" intake pipe
32
DES3
Series
Roof
(Flexible boot and band
clamps are recommended)
Burner