Configuration parameters

Shutdown parameters

Follow these shutdown principles when configuring the shutdown parameters:
The Shutdown initiated after (SIA) value entered for the UPS Network Module must be equal to or
greater than the HPPP Client configured with the longest SIA time. Otherwise, the Client starts to
shutdown at the same time as the UPS Network Module.
The Operating system shutdown time (OST) value entered for the UPS Network Module must be equal
to or greater than the HPPP Client configured with the longest OST. Otherwise, it is automatically
replaced by the longest OST when the Client is connected. The updated value is displayed on the
Shutdown Parameters screen for the UPS Network Module.
After the operating system shutdown begins, the shutdown process cannot be canceled, even if utility
power is restored.
For load shedding, each Client is shutdown based on its own delay settings. This increases the backup
time for the remaining Clients.
The UPS Network Module waits until the operating system is shut down before powering down the load
segments.
The UPS is powered down after all load segments are powered down.
If any other condition, such as the Remaining Backup time under or Battery capacity under value being
reached occurs during the SIA time, the UPS Network Module starts the shutdown process earlier.
Configuration parameters 52