Connecting the ERM to the UPS

NOTE: To install a second ERM, plug the cable from
the second ERM into the socket at the rear of the first
ERM. Up to two ERM units can be connected.

Switching on the ERM circuit breaker

Charging the ERM batteries

Connect the UPS to a grounded utility power outlet. When the
UPS is plugged in, it automatically enters Standby mode and
begins charging the ERM batteries. With the UPS in Standby
mode, allow the ERM batteries to charge for at least 24 hours
before putting the UPS into service.
CAUTION: To ensure maximum runtime, be sure to
configure the UPS for the number of installed ERMs
using the UPS front panel controls.

Configuring the UPS

After the ERMs are installed, place the UPS in Configure
mode, and use the UPS front panel controls and LED
indicators to configure the UPS for the number of attached
ERMs. Other UPS parameters that can also be configured
are the nominal utility voltage level and Site Wiring
Fault detection.
In Configure mode, the LED front panel display changes
function to enable modification of the UPS parameters. Each
LED is associated with a different parameter.
Available
Parameter
settings
Nominal
200/208
Voltage
Nom
Setting
220 Nom
230 Nom
240 Nom
Wiring
Wiring Fault Utility
Fault
Setting
ERM
0 ERMs
Setting
1 ERM
2 ERMs
To change the UPS configuration parameters:
Place the UPS in Configure mode.
1.
The LEDs associated with the currently configured
parameters illuminate. A flashing green cursor indicates
where you are in the configuration process as you scroll
through the available settings.
To change the nominal voltage, press the On button to
2.
advance the cursor to the LED associated with the
appropriate nominal voltage parameter. The selected
voltage configuration LED flashes.
Associated
Explanation (when LED is
LED
illuminated)
General
Nominal utility voltage
Alarm
level is set to 200/208
(red)
VAC (factory default for
326529-D71)
On
Nominal utility voltage
Battery
level is set to 220 VAC
(red)
Battery
Nominal utility voltage
Fault (red)
level is set to 230 VAC
(factory default for
326529-B31)
Site
Nominal utility voltage
Wiring
level is set to 240 VAC
Fault (red)
Audible alarm sounds
(green)
when ground is missing or
line and neutral
connections are reversed
0% to
UPS is configured for no
25% load
attached ERMs (factory
(green)
default)
26% to
UPS is configured for 1
50% load
attached ERM
(green)
51% to
UPS is configured for 2
75% load
attached ERMs
(green)