Discharge Pipe Temperature Control - Daikin FTXN-LV Troubleshooting Manual

Inverter split wall mounted type l-series
Table of Contents

Advertisement

-
The compressor frequency is adjusted based on coil temperature:
During cooling mode – outdoor coil temperature.
During heating mode – indoor coil temperature.
-
This protection is activated when the coil temperature > 64°C, the compressor stop and OD fan stop after
30s.
-
The unit can only be restarted after 3 minutes.

DISCHARGE PIPE TEMPERATURE CONTROL

Used as a measure of the compressor's internal temperature.
-
-
Compressor frequency is control to keep this temperature from going up further when it rises above a
certain level.
-
If compressor discharge temperature >102°C (111°C) for the first time, this control starts and set the
current frequency as upper limit. At the same time, running frequency start to reduce by 1 step and so on,
until temperature falls between 99°C (109°C)and 90°C (107°C) – at the maintain zone.
-
This protection is activated when the compressor discharge temperature > 110°C (120°C). The
compressor will stop and considered trip.
-
If the compressor discharge temperature < 90°C (107°C), the compressor frequency will be reset based
on the OD ambient, set and room temperature.
TS13-01 Troubleshooting manual
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxn-lv

Table of Contents