ROTATION REGULATING FUNCTIONS
Command Rotation
Starting Rotation
∆T
Defrost*
* Defrost control for heat pump model only
STARTING ROTATION
STARTING CONTROL
-
To avoid excessive oil discharge from compressor or to promote oil lubrication during startup.
-
To prevent liquid flood back to the compressor.
-
To limit starting current.
-
When compressor starts to rotate from OFF to ON, compressor rotation is set to run gradually to each
upper limit at a specific timer setting.
Model
RXN25LV1B
RXN35LV1B
RXN50LV1B
TS13-01 Troubleshooting manual
Upper limit rotation
Limit Rotation
Lower limit rotation
Max. f
68 Hz
74 Hz
90 Hz
Target Rotation
10