Daikin FTXN-LV Troubleshooting Manual page 11

Inverter split wall mounted type l-series
Table of Contents

Advertisement

RXN60LV1B
COMMAND ROTATION
-
Cut in upon termination of Starting Control.
-
Achieve capacity control by controlling the compressor rotation based on :
Temperature difference between set and room temperature, T.
Limit Rotation.
Defrost control.
Fuzzy Control
Based on temperature difference, T, current fan speed setting & current indoor operating mode at every
-
30 seconds interval.
-
Condition 1
∆T
t
Use to set target for compressor frequency change
LIMIT ROTATION
Determine from
Upper limit rotation
TS13-01 Troubleshooting manual
93 Hz
Temperature Difference
∆T
= T
- T
room
set
Compressor frequency is increased or
decreased
Condition 2
d∆T
d∆T
= ∆T
- ∆T
t
t
t-1
11