Heat / Cool Connections
Fault Input
Aux
Remote
T1
Sensor
T1
T0
Remote
Override
T0
Cool 1
Cool 2
Heat 1
Heat 2
Heat 3
Fan
Heat Pump Connections
Fault Input
Aux
T1
Remote
Sensor
T1
T0
Remote
Override
T0
Compressor 1
Compressor 2
Rerversing Valve
Auxilary Heat
Fan
Specifications
Range:
5° to 35° c.
Deadband:
1~5 deg C
Alarms:
2~45 deg C
After Hours:
0~4 Hours
Cal Offset:
+/- 6 C
Resolution:
1°c
Accuracy:
+/- 0.3°c
Load rating:
2 Amps @ 24 VAC max.
Lithium Bat:
10 Years
(Or 8 weeks accumulated power outage)
Voltage:
24VAC.
Connectors:
Screw type.
Material:
PC/ABS
Weight:
210g
Size:
82 x 140 x 27
Warranty:
1 year R.T.B
Rev G June 2007
Electrical Diagram
Flat cable connector
ISIS
24 Volt Control
Y1 Y2 W1 W2 W3
G1 N/A
AL AL Rc
Rh
C
Flat cable connector
ISIS
24 Volt Control
O/B
Y1 Y2
W2 W3
G1 N/A
AL AL Rc
Rh
C
Optional 240V Interface available
(Adjustable)
(Adjustable)
(Adjustable)
(Adjustable)
Optional Smart Pak Cover Shown
Link must be installed
between RH &RC
24V Active
24V Common
Alarm Output
Dry Contact (Max 24V)
Link must be installed
between RH &RC
24V Active
24V Common
Alarm Output
Dry Contact (Max 24V)
Smart Pak
Smart Temp
ISIS Heat Cool Configuration
Jumper
Jp4
JP3
Jp5
Position
4 min
Clock
Off
N/A
Time
24 Hour
Delay
Time
Clock
On
N/A
Delay
AM/PM
Off
Position A = Internal Sensor
JP-1
Position B = Remote Sensor
ISIS Heat Pump Configuration
Jumper
Jp4
JP3
Jp5
Position
4 min
Clock
Off
N/A
Time
24 Hour
Delay
Time
Clock
On
N/A
Delay
AM/PM
Off
Position A = Internal Sensor
JP-1
Position B = Remote Sensor
JP7 Fan / RV Select
Jp6 Heat Pump / Heat Cool select
JP 5 Factory USE ONLY - N/A
Jp4 12/24 hour clock
Jp3 Compressor Protection
Jp1
Internal or
Remote Sensor
Battery
B
Holder
A
Optional Adjustable Remote Sensor
(Non Adjustable and Duct Mount Sensors available)
Smart Temp
Smart Temp Australia Pty Ltd
Unit 20, 1488 Ferntree Gully Road
Knoxfield 3180 Victoria Australia
Phone:(03) 9763 0094 Fax (03) 9763 0098
www.thermostat.com.au
Australia
Making Life Comfortable
JP6
JP7
Must be
Fan ON
immediate
in this
with Heat call
position
(Elec. Heat)
Fan controlled
by plenum switch
(Gas. Heat)
JP6
JP7
Rev Valve
Energize "O"
(cooling)
Must be
Rev Valve
in this
Energize "B"
position
(heating)
Need help?
Do you have a question about the ISIS and is the answer not in the manual?