Indoor Unit
Air Intake
Grille
Air Intake
Air Discharge
Nozzle
Outdoor Unit
The outdoor unit must be installed in such a way, so as to
prevent short circuit of the hot discharged air or obstruc-
tion to the smooth air flow. Please follow the installation
clearances shown in the figure. Select the coolest possible
place where intake air temperature is not greater than the
outside air temperature (maximum 45°C).
Installation clearances
Dimension
A
Minimum Distance,
300
mm (in)
(11.8)
Note: If there is any obstacle higher than 2m, or if there is
any obstruction at the upper part of the unit, please allow
more space than the figure indicated in the above table.
B
A
C

INSTALLATION DIAGRAM

Air Filter
Indicator
Drain Hose
Lights
Signal Receiver

INSTALLATION OF THE OUTDOOR UNIT

B
C
D
1000
300
500
(39.4)
(11.8)
(19.7)
D
Front Frame
Back Housing
ON/OFF Switch
Condensed Water Disposal of Outdoor Unit
(Heat Pump Unit Only)
There are 2 holes on the base of Outdoor Unit for
condensed water to flow out. Insert the drain elbow to
one of the holes.
To install the drain elbow, first insert one portion of the
hook to the base (portion A), then pull the drain elbow
in the direction shown by the arrow while inserting the
other portion to the base. After installation, check to
ensure that the drain elbow clings to base firmly.
If the unit is installed in a snowy and chilly area, con-
densed water may freeze in the base. In such case,
please remove plug at the bottom of unit to smooth the
drainage.
PLUG
A
BASE
DRAIN
ELBOW
1-3
Refrigerant Piping
DRAIN
ELBOW
Please remove side
plate when connect-
ing the piping and
connecting cord
PUSH & PULL UP