KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
7

Commissioning

7.1

Software

Note
The devices are products of the KNX system and meet KNX guidelines. Detailed expert knowledge
by means of KNX training sessions for a better understanding is assumed.
To start the device a physical address must be assigned first. The physical address is assigned and the
parameters are set with the Engineering Tool Software ETS (from version ETS 3.0 f). Use the appropriate
commissioning tool (Power-Tool) for the parameter settings.
7.1.1

Preparatory steps

1. Connect a PC via the KNX interface, e.g. the commissioning interface / adapter 6149/21-500, to the KNX bus
line. The Engineering Tool Software ETS (from version ETS 3.0 f) must have been installed on the PC.
2. Switch on the bus voltage.
7.1.2

Assigning a physical address

1. Press the two top buttons (1) on the device
simultaneously.
The message "PROG" (2) appears in red on the display.
2. After the physical address has been programmed, the
message "PROG" goes out.
Video for assigning the physical address.
KNX Technical Reference Manual | 1473-1-7819
Commissioning
Fig. 8:
Assigning a physical address
— 17 —