Powerware 5115 User Manual page 43

Tower ups 500–1400 va
Hide thumbs Also See for 5115:
Table of Contents

Advertisement

Table 7. Battery
Configuration
Voltage
Type
Charging
Monitoring
Table 8. Battery Run Times (in Minutes)
Load (VA)
Watts
200
300
500
600
750
900
1000
1200
1400
Battery times are approximate and may vary depending on the load configuration and battery charge.
NOTE
Powerware
5115 Tower UPS (500–1400 VA) User's Guide
®
500 VA: (1) 12V, 9 Ah internal battery
750 VA: (2) 12V, 7 or 7.2 Ah internal batteries
1000 VA: (2) 12V, 9 Ah internal batteries
1400 VA: (3) 12V, 9 Ah internal batteries
500 VA: 12 Vdc
750–1000 VA: 24 Vdc
1400 VA: 36 Vdc
Sealed, maintenance-free, valve-regulated, lead-acid
Advanced charging for faster recovery; approximately 3 hours to 90% usable
capacity at nominal line and no supplementary power supply load
Advanced monitoring for earlier failure detection and warning
500
128
17
192
11
320
5
402
503
603
670
804
938
UPS Models by VA Ratings
750
1000
38
41
27
28
14
15
9
10
6
05146640 Rev C www.powerware.com
S
Specifications
1400
58
41
28
19
8
14
6
10
5
8
6
5
37

Hide quick links: